Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface
FAULT DESCRIPTION CORRECTIVE ACTION
Automatic Reset
High Limit / HEX-
Temp SW
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
display to reset.)
Either the auto-reset high limit, or the
O-temp heat exchanger switch has opened.
Automatic Reset High Limit:
Verify that the system is full of water and that all air
has been properly purged from the system.
Verify that the water heater is piped properly into the
heating system. Refer to Section 6 - System Piping
of the Armor X2 Installation and Operation Manual for
the proper piping methods for the Armor X2.
Check voltage to water heater pump motor on a call
for heat. If voltage is not present, check wiring back
to the pump relay.
Replace the pump relay if necessary.
If 120 VAC is present on a call for heat and the water
heater pump is not operating, replace the pump.
Check resistance of water sensors and compare to
Table 3B on page 40 of this manual. Replace sensor
if necessary.
Replace outlet sensor.
HEX Temp SW:
Check continuity across two contacts. Wires should
be connected at both poles of normally closed switch.
Inspect the rear of the inner combustion chamber
at the burner level, for refractory breakdown/missing.
Replace the refractory if no damage to the heat
exchanger as a result of the burner, otherwise,
replace the heat exchanger.
Faulty O-temp heat exchanger switch. Replace
switch.
Blower RPM’s
Too Low
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
display to reset.)
The actual fan rpm is 30% lower than what
is being called for. Reference the Burners
Screen information on page 28 of this
manual.
Vent/air intake lengths exceed the maximum allowed
lengths. Refer to Section 3 - General Venting of the
Armor X2 Installation and Operation Manual for
proper lengths.
Check for obstruction or blockage in the vent/air
intake pipes or at terminations.
• Check the wiring connections at the fan and at the
main control board.
Replace the fan.
Replace the main control board.
Blown fuse.
Replace fuse F4 on the control board, see page 38 of
this manual.