Boiler User Manual

3 Troubleshooting (continued)
Service Manual
43
Table 3G (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
FAULT DESCRIPTION CORRECTIVE ACTION
Flame Failure
Running 2
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
SMART TOUCH
display
to reset.)
The unit was running and lost the flame
signal.
Inspect flame rod 2 and associated wiring for damage
and connection. Reference page 34 of this manual for
removal and cleaning procedures. Replace if
necessary.
Check for proper electrical grounding of unit.
Check incoming supply gas pressure. Natural and
L.P. gas pressures should be between 4 - 14 inches w.c.
(1.0 - 3.5 kPa). Refer to Section 6 - Gas Connections of
the Crest Installation and Operation Manual for detailed
information concerning the gas supply.
• Verify that the plastic hose from the gas valve to the air
inlet is connected and is not damaged.
• Verify that the vent/air intake pipes are installed correctly
and there are no obstructions.
• Inspect flame sensor and associated wiring. Reference
page 34 of this manual for removal and cleaning
procedures. Replace if necessary.
• Check combustion.
Inspect the burner. Reference page 34 of this manual for
removal and cleaning procedures. Replace if
necessary.
Gas Valve / Relay
Failure 1
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
SMART TOUCH
display
to reset.)
The main control board did not detect gas
valve 1.
Check wiring harness connection at the gas valve and
at the main control board.
Replace the gas valve wire harness.
Replace the gas valve.
Gas Valve / Relay
Failure 2
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
SMART TOUCH
display
to reset.)
The main control board did not detect gas
valve 2.
Check wiring harness connection at the gas valve and
at the main control board.
Replace the gas valve wire harness.
Replace the gas valve.