3 Troubleshooting (continued)
Table 3G (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
FAULT DESCRIPTION CORRECTIVE ACTION
Blower Proving
Switch Open 2
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
display to reset.)
Pressure switch contacts are open.
Check the wiring connections to switch. Wires should
be connected to the common and normally open
terminals.
• Remove switch and check for blockage in the orifice.
Vent/air intake lengths exceed the maximum allowed
lengths. Refer to Section 2 - General Venting of the
Crest Installation and Operation Manual for
proper lengths.
Check for obstruction or blockage in the vent/air
intake pipes or at terminations.
• Inspect the burner. Reference page 34 of this manual
for removal and cleaning procedures. Replace if
necessary.
Verify combustion air blower 2 is operating. Replace if
necessary.
Inspect the heat exchanger. Reference page 35 of
this manual for removal and cleaning procedures.
Faulty pressure switch. Replace switch.
Burner Supply
Temperature
Differential
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
display to reset.)
Combustion air to burner 1 temperature
is higher than combustion air to burner 2
temperature or vice versa.
• Inspect the combustion air temperature sensor and
associated wiring.
Measure the resistance of the combustion air
temperature sensor and compare to Table 3E on
page 38 of this manual
Replace the sensor if necessary.
Verify that the vent / air intake pipes are properly
installed and that there are no obstructions.
Burner Supply
Temperature
High 1
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
display to reset.)
Combustion air temperature is very high.
Check if the vent backflow preventer is installed for
boilers commonly vented.
• Check if the vent backflow preventer is stuck open
while the unit is off.
• Inspect the combustion air temperature sensor and
associated wiring.
Measure the resistance of the combustion air
temperature sensor and compare to Table 3E on
page 38 of this manual.
• Replace the sensor if necessary.
Burner Supply
Temperature
High 2
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
display to reset.)
Combustion air temperature is very high.
Check if the vent backflow preventer is installed for
boilers commonly vented.
• Check if the vent backflow preventer is stuck open
while the unit is off.
• Inspect the combustion air temperature sensor and
associated wiring.
Measure the resistance of the combustion air
temperature sensor and compare to Table 3E on
page 38 of this manual.
• Replace the sensor if necessary.
Service Manual