Service Manual

1 Service
16
Service Manual
1 Service
Parameter table (continued)
Table 1D (continued from previous page) This table lists SMART SYSTEM control module parameters and
where to access them
The parameters for Building Management System operation are not listed in this table. They are only
accessible using the PC interface software. See separate documentation for access information. See page
21 of this manual for a brief discussion.
NOTICE
MENU SUB ITEM DESCRIPTION
SEE
PAGE
USER ACCESS INSTALLER ACCESS
DISPLAY MODIFY DISPLAY MODIFY
G
1 Anti-cycling Time 20 No No Yes Yes
2
Return Temperature Differential
for Ending Anti-Cycling
20 No No Yes Yes
3 Ramp Delay On/Off 20 No No Yes Yes
ANTI-CYCLING
H
1
SH Controlling Sensor
(Outlet/System, Inlet)
21 No No Yes Yes
2
SH Source (Thermostat, BMS,
and Cascade)
21 No No Yes Yes
3 Boiler Cascade Address 21 No No Yes Yes
4 Max. Cascade Set Point 21 No No Yes Yes
5 Cascade Offset 22 No No Yes Yes
6 Cascade Differential 22 No No Yes Yes
CONTROL
MODES
I
1 System Pump Delay 22 No No Ye s Yes
2 SH Pump Delay 22 No No Ye s Yes
3 DHW Pump Delay 22 No No Yes Yes
CIRCULATION
PUMPS
J
1 Service Notification in Month 22 No No Yes Yes
2
Service Notification Running
Hours
22 No No Ye s Yes
3 Service Notification Boiler Cycles 22 No No Ye s Yes
4 Reset Service Notification Counter 22 No No Ye s Yes
SERVICE
NOTIFICATION