KNIGHT DHW PUMP RECOMMENDATION TABLE
Tank Tank Tank Tank Tank Tank
SIT030 SIT040 SIT050 SIT065 SIT080 SIT119
Flow Head Flow Head Flow Head Flow Head Flow Head Flow Head
Boiler Rate Loss Pump Rate Loss Pump Rate Loss Pump Rate Loss Pump Rate Loss Pump Rate Loss Pump
GPM Ft/Hd GPM Ft/Hd GPM Ft/Hd GPM Ft/Hd GPM Ft/Hd GPM Ft/Hd
KBN081 5.0 11.36 PUM3020 5.0 11.41 PUM3020 5.0 11.46 PUM3020 5.0 11.61 PUM3020 5.0 11.61 PUM3020 5.0 11.73 PUM3020
Flow Head Flow Head Flow Head Flow Head Flow Head Flow Head
Boiler Rate Loss Pump Rate Loss Pump Rate Loss Pump Rate Loss Pump Rate Loss Pump Rate Loss Pump
GPM Ft/Hd GPM Ft/Hd GPM Ft/Hd GPM Ft/Hd GPM Ft/Hd GPM Ft/Hd
KBN106 5.0 8.86 PUM3020 5.0 8.91 PUM3020 5.0 8.96 PUM3020 5.0 9.11 PUM3020 5.0 9.11 PUM3020 5.0 9.23 PUM3020
8.0 18.91 PUM3020 8.0 19.04 PUM3020 8.0 19.18 PUM3020 8.0 19.57 PUM3020 8.0 19.57 PUM3020 8.0 19.87 PUM3020
Flow Head Pump Flow Head Flow Head Flow Head Flow Head Flow Head
Boiler Rate Loss Rate Loss Pump Rate Loss Pump Rate Loss Pump Rate Loss Pump Rate Loss Pump
GPM Ft/Hd GPM Ft/Hd GPM Ft/Hd GPM Ft/Hd GPM Ft/Hd GPM Ft/Hd
KBN151 5.0 5.36 PUM3020 5.0 5.41 PUM3020 5.0 5.46 PUM3020 5.0 5.61 PUM3020 5.0 5.61 PUM3020 5.0 5.73 PUM3020
8.0 10.11 PUM3020 8.0 10.24
PUM3020 8.0 10.38 PUM3020 8.0 10.77 PUM3020 8.0 10.77 PUM3020 8.0 11.07 PUM3020
12.0 16.06 PUM3020 12.0 16.34 PUM3020 12.0 16.67 PUM3020 12.0 17.53 PUM3020 12.0 17.53 PUM3020 12.0 18.22 PUM3020
Flow Head Flow Head Flow Head Flow Head Flow Head Flow Head
Boiler Rate Loss Pump Rate Loss Pump Rate Loss Pump Rate Loss Pump Rate Loss Pump Rate Loss Pump
GPM Ft/Hd GPM Ft/Hd GPM Ft/Hd GPM Ft/Hd GPM Ft/Hd GPM Ft/Hd
KBN211 8.0 7.91 PUM3020 8.0 8.04 PUM3020 8.0 8.18 PUM3020 8.0 8.57 PUM3020 8.0 8.57 PUM3020 8.0 8.87 PUM3020
12.0 12.36 PUM3020 12.0 12.64 PUM3020 12.0 12.97 PUM3020 12.0 13.83 PUM3020 12.0 13.83 PUM3020 12.0 14.52 PUM3020
16.0 23.66 ARM3045PBF 16.0 24.16
A
RM3045PBF 16.0 24.74
A
RM3045PBF 16.0 26.27 ARM3045PBF 16.0 26.27
A
RM3045PBF 16.0 27.50
A
RM3045PBF
Flow Head Flow Head Flow Head Flow Head Flow Head Flow Head
Boiler Rate Loss Pump Rate Loss Pump Rate Loss Pump Rate Loss Pump Rate Loss Pump Rate Loss Pump
GPM Ft/Hd GPM Ft/Hd GPM Ft/Hd GPM Ft/Hd GPM Ft/Hd GPM Ft/Hd
KBN286 12.0 7.06 PUM3020 12.0 7.34 PUM3020 12.0 7.67 PUM3020 12.0 8.53 PUM3020 12.0 8.53 PUM3020 12.0 9.22 PUM3020
16.0 12.16 PUM3020 16.0 12.66 PUM3020 16.0 13.24 PUM3020 16.0 14.77 PUM3020 16.0 14.77 PUM3020 16.0 16.00 PUM3020
20.0 16.71 PUM30001 20.0 17.49 PUM30001 20.0 18.40 PUM30001 20.0 20.80 PUM30001 20.0 20.80 PUM30001 20.0 22.71 PUM30001
For Knight Fire Tube boilers (WHN055-399), use PUM3020 for all models from 5 to 20 GPM flow rates.
Notes:
The chart includes recommended Gallon Per Minute flow rate, calculated Head Loss and recommended Pump.
The GPM, Ft/Hd and Pump selection is based on the boiler and the tank coil connected with maximum 20 feet of straight pipe, 4 - 90° elbows and 2 - full port ball valves.
See the Installation and Operation manual for more details including pipe diameters and piping diagrams.
Squire Indirect Storage tanks are for residential use only. Do not install Squire tanks in commercial applications with Knight XL or SYNC boilers.