TDS
LOCTITE
®
Fire Block Foam
Page 1 of 7
Revision: April 1, 2023
Supersedes: NEW
Ref. #:607448
Technical Data Sheet
Fire Block Foam
LOCTITE
®
Fire Block Foam is a specially designed, closed cell, insulating foam used to fill
gaps and resist the migration of fire and hot gasses in Type V residential (wood frame)
construction. This foam is orange in color and easily identifiable on the jobsite. Best for use
where a fire rated foam is needed such as electrical, plumbing, and HVAC penetrations. Fire
Block Foam is UL Certified and ASTM tested.
Available as:
Item #
Package
Size
Color
2866858
Metal Aerosol
Cannister
12 oz. (340 g)
Orange
• Specially formulated for fire blocking applications
• Orange color identifies Loctite Fire Block Foam as an approved fire block product for
Type V construction
• Fire rated and tested in accordance to:
• UL 723 in accordance with ASTM E84
• ASTM E814 (modified)
• NFPA 286
• Conforms to IRC (International Residential Codes) and IBC (International Building Code)
fire blocking requirements
Loctite Fire Block Foam is designed specifically to help prevent the spread of fire and smoke through concealed service
penetrations in Type V construction, and occupancy groups R3 and R5 buildings, in accordance with fire blocking requirements
outlined in the International Residential Code and International Building Code. "Fire blocking" is defined by the IBC as the use
of approved building materials installed in concealed spaces to resist the migration of fire and hot gases. Fire Block Foam may
also be used for gap filling purposes around wiring and plumbing penetrations, HVAC duct work, basement and crawl space
drafts, sill plate, attic hatch, and is for both interior and exterior use.
• Not for use as a “firestop” product and should not be used in hourly fire rated assemblies that require fire stop products
• Not for use in Type I through Type IV construction
• Some local building codes may restrict the use of polyurethane foams as “fireblocks”. Always check local building codes.
• Do not cut foam. The fire-blocking capabilities are greatly compromised if foam is cut or damaged.
• Should not be used in contact with chimneys, heater vents, steam pipes, or other areas which could be subjected to
surface temperatures greater than 187°F
• For cold weather application, product should be stored above 41°F (5° C) at least 12 hours before application
• Despite significantly higher UV resistance, it is still recommended to protect the foam from UV radiation. Exposed foam
should be coated with a protective covering or coating
• Do not store product on its side; cans must be stored upright at all times
• Does not bond polyethylene, polytetrafluoroethylene (PTFE)/Teflon
®
or siliconized surfaces
• Certain materials such as rubbers and plastics may have bonding difficulties. Test before use
• Flexible sheet goods
DESCRIPTION
FEATURES & BENEFITS
RECOMMENDED FOR
LIMITATIONS