Instructions / Assembly






ProPer exhaust requires adequate intake!!!














 
  
 
 
 
 
 
 




lomanco.com


DO install all Exhaust Ventilation at the SAME HEIGHT
within a common attic area. Installation of exhaust
vents at more than one level on a roof allows the upper
exhaust vent to wrongly pull air in from lower exhaust
vent rather than from the soft Intake Vents.
DON’T install exhaust vents at different heights.
DON’T install Ridge Vents down the hip.
DO install ONLY ONE TYPE of Exhaust Ventilation within
a common attic area. Exhaust Vents pull air from the
easiest Intake source. The use of two or more types
of exhaust vents such as Power Vents with Roof Vents
or Gable Vents with Ridge Vents or Roof Vents could
make one of these vents act as intake instead of pulling
air from the soft vents.
DON’T mix different types of exhaust vents.
DO install a BALANCED SYSTEM of Intake and Exhaust
Ventilation. 50% Intake and 50% Exhaust is a balanced
system. Improper intake will usually lead to snow or
rain inltration into the exhaust vents.
Tools needed:
Screwdriver
Carpenters level
Key hole saw
Or saber saw
Putty Knife
Utility Knife
Drill
Hammer
Ruler