Installation Instructions

1
APPLICATION INSTRUCTIONS
G
At the time of manufacture, siding meets or exceeds the
performance standards set forth in ICC-ES AC321 and has
achieved code recognition under ESR-1301, CCMC 11826-L,
APA recognition under PR-N124, and HUD recognition under
HUD-MR# 1318c. For copies of Product Approvals go online at
https://lpcorp.com/resources/product-literature/or call LP
Customer Support at 888-820-0325.
Panel siding with SilverTech or SmartFinish is specifi cally for
sheds and other outdoor structures where the interior wall
cavities will remain permanently exposed.
Non-grooved square edge panel siding may be installed vertically
or horizontally. Shiplap edge panel siding is limited to vertical
applications.
(Figure 5E, 5F and 5G)
Minimum 6 inch (152 mm) clearance must be maintained
between siding and finish grade (ground cover).
Siding applied adjacent to surfaces such as porches, patios,
balconies, or walking surfaces (including porch columns) must
have a clearance of at least 1 inch (25 mm) above any horizontal
surface. Clearance may be reduced to 3/8 inch (10 mm) for:
- Porches, patios, balconies, or walking surfaces that slope
away from the structure or the surface provides gaps that
allow water to fl ow through so that it cannot accumulate,
and are covered by a roof, not an eave or overhang; or
- Porch columns with walking surfaces that slope away from
the structure or the surface provides gaps that allow water
to fl ow through so that it cannot accumulate.
Minimum 1 inch (25 mm) clearance at intersection with roof line.
Apply and maintain siding in a manner that prevents moisture
intrusion and water buildup.
All wood substrate that is exposed to the weather must be
sealed in a manner that prevents moisture intrusion and water
build up.
- Seal ALL exposed cuts of siding and trim. Field spray
applied coatings on cuts are not recommended.
- Sealing can be accomplished by applying a paint or
sealant according to the manufacturer’s requirements.
LP does not recommend panel siding for use in ICF assemblies.
If used, LP will NOT warrant for Buckling and Shrinkage.
Use nails to fasten panel siding to structural framing.
- Alternate fasteners such as staples are permissible when
allowed by local building code and where the size,
embedment, placement and number of alternate fasteners
fasteners are designed by a licensed design professional
and approved by the local building o cial.
- LP will not consider any warranty claims for damage or
performance failures to the extent caused by the use of
any alternate fasteners.
SIDING MUST NOT BE IN DIRECT CONTACT WITH MASONRY,
SUCH AS, BUT NOT LIMITED TO CONCRETE, BRICK, STONE,
STUCCO OR MORTAR.
®
38, 76 AND 190 SERIES
SMOOTH FINISH OR CEDAR TEXTURE
PRIMED & PREFINISHED PANEL SIDING
(including SilverTech & SmartFinish)
M
Moisture control and water vapor control are critical elements
of proper housing design. Check your local building code for
application procedures for handling moisture and water vapor.
As with all wood products, do not apply engineered wood siding
to a structure having excessive moisture conditions such as
drying concrete, plaster or wet blown cellulose insulation.
Siding must not be applied to green or crooked structural
framing members.
Siding must not be applied over rain-soaked or buckled
sheathing materials.
Gutters are recommended for control of roof water run o .
Panel siding with a shiplap joint must be installed with the
long dimension vertically on studs.
- 38 and 76 Series panel siding may be installed directly to
studs spaced a
maximum of 16 inch (406 mm) o.c.
- 190 Series panel siding is required when installing directly
to studs spaced up to a maximum of 24 inch (610 mm) o.c.
S S
• Handle prefi nished panel siding with extreme care during
storage and application.
Keep siding clean and dry. Inspect prior to application.
Store o the ground on a fl at surface and under a roof or
separate waterproof covering.
- Additional support may be required to achieve a safe
clearance from the ground.
- When the covering is removed, cut all unit banding.
When unpackaging prefi nished siding products, cut the full
length of the shrink-wrap to avoid dragging and scu ng of
the trim or sidings painted surface.
- All movement or transportation of siding products on the
jobsite should be done with slip sheets intact.
- DO NOT remove slip sheets placed between the trim or
siding painted surfaces until each piece is being prepared
for installation.
- Early removal of the slip sheets will leave siding products
exposed to possible paint damage before installation.
Touch up any damage to prefi nished siding that may occur
during application per the Finishing section in this document
or per the Prefi nishers specifi cations.
S  H
G
(CONT.)