Fire Detection Control Panels Specification Sheet

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
BC06_DBL_LST_EN_0826.PDF • PAGE 2
ABuilding Safety. Building Security.
Clear Concept
The Fire Detection Control Panels BC06-1 and BC06-2
have been designed for use in small re detection sys-
tems and already in the basic version they provide the
following features:
4 conventional detector lines permit the connection
of automatic detectors and manual call points in con-
ventional technology as well as special detectors with
contact output. Each detector line can be individually
parameterised as detector zone for fi re alarms or as
detector zone for fault messages.
If automatic detectors and manual call points are con-
nected together on one detector line, their activati-
ons can be differentiated and evaluated differently by
the control panel. To this aim, the manual call points
must be equipped with a special coding module.
A slot for connecting the Zone Extension Board
ZEB2-1 is available to facilitate the extension to 6
conventional detector lines.
The installation of the zone extension board is auto-
matically detected by the control panel and the corre-
sponding parameters are set to initial values.
Two individually monitored, separately activated siren
outputs with an output current of 1A and 0.5A respec-
tively, allow for the connection of acoustic or optical
signalling devices. When parameterised accordingly,
the siren outputs can also be operated as evacuation
circuits.
Dry relay outputs indicate the alarm and fault conditi-
ons of the control panel. In addition, 8 open-collector
outputs with fi xed preset functions as well as two au-
xiliary inputs whose parameters can be freely set are
available for general control tasks.
Logical combinations of detector zones for the acti-
vation of external alarming devices allow for a high
degree of exibility. Thus, no additional expenses
arise for external relays or logic gates. Thanks to the
wide range of parameterisation possibilities, individu-
al requirements even under the most diffi cult ambient
conditions can be combined into a reasonable re
protection strategy.
All events that occur can be output in English via a
connected printer or PC. Thus, all system conditions
and user operations that occurred are documented in
a clearly laid out way.
The Fire Detection Control Panel BC06-2 includes a
4-digit, non-resettable alarm counter which indicates
the total number of alarms by means of an LC display
in the operating fi eld.
A possible breakdown of the central processing board
is securely detected and displayed by the system.
The processor-monitored power supply ensures per-
manent supervision and charging of the batteries.
This way, even during a power failure the untroubled
and uninterrupted operation (for more than 72 hours
depending on the design of the batteries) is guaran-
teed.
Three hierarchised authorization levels for operation
and parameterisation provide a high degree of secu-
rity against unauthorized access.
The control panel is easily operated and the parame-
ters are set via the display and operating eld. LEDs
indicate the current menu and the selected parame-
ter. This facilitates user guidance during commissio-
ning, operation and maintenance.
The initial commissioning of the control panel is sig-
nifi cantly facilitated by the practical factory settings.
This guarantees easy and time-saving commissio-
ning.
The extremely at wall-mount cabinet allows for an easy
mounting in virtually any place of the building. Thanks to
its modern, ageless design, architectural requirements
and demands of the respective regulations are ideally
combined. Thanks to the compact design, the standard
case can accommodate batteries with up to 7Ah also
in the event of full extension (central processing board,
optional zone extension board and an auxiliary module)
of the control panel. Series BC06 thus stands for modu-
larity and easy expansion.
This product complies with all relevant standards of
EN 54 and is tested by the VdS. LST‘s high quality level
is secured by a permanently monitored quality manage-
ment system certifi ed to ISO 9001.