Detector Relay Base Specification Sheet

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
ECO1000BREL24L_DBL_LST_EN_0804.PDF • PAGE 1
ABuilding Safety. Building Security.
Detector Relay Base
ECO1000BREL24L
Description
Specifi cations
The Detector Relay Base ECO1000BREL24L with inte-
grated relay output is designed for the easy connection
of automatic detectors Series ECO1000. Due to its ro-
bust multi-wire screw terminals, the detectors can be
wired with ease, thus achieving a secure and durable
connection.
The relay output is activated through the alarm activati-
on of the inserted detector and remains active until the
alarm is reset on the re detection control panel. The
application has to comply with the guidelines in the LST
Connection of Detectors.
During construction work (or when the detector has
been removed) the detector line can be connected
through via an auxiliary contact, which is integrated
into the base. With that, the whole wiring of the detec-
tor line can be examined without risking contamination
of the detectors. The contact is automatically opened
by installing the detector.
The base is designed for surface mounting in dry
rooms. A mechanical theft protection of the detector
can optionally be activated at the detector base.
Suitable for automatic detectors in
conventional technology
Relay output with dry change-over
contact
Screw terminals for secure
connection of multiple wires
Test contact for examining the
detector line without detectors
Mechanical theft protection can be
activated
Operating voltage Supply through the detector line voltage
Current consumption 1µA (quiescent), 30mA (active)
Contact rating 1A at 30VDC
Ambient temperature -30°C to +70°C
Relative humidity 5 – 93% (no condensation)
Dimensions ø × H 102.5 × 33 (mm)
Colour white
Weight 70g
Order number 246141
Order name Detector Relay Base/Conv./1000/SS ECO1000BREL24L