Maintenance Object Repair Procedures
Page 10-717EXT-DEV ADMIN? Y (External Device Alarm)
10
ANY FAIL The External Device Alarm has been activated by the
external device.
1. Clear the major alarm on the external device, and
rerun the test.
2. If the test still fails, then disconnect the External
Device Alarm Leads from the Maintenance circuit
pack and rerun the test.
3. If the test still fails, then there is a problem with the
analog external device alarm port or the
Maintenance circuit pack that is reporting the alarm.
This circuit pack should be replaced. There are
failures that can occur on the Maintenance circuit
pack that
will not
be detected by their respective
maintenance, but which will cause many
environment tests to fail. If many environment tests
are failing, the suspect circuit pack should be
replaced and the test rerun.
4. If the test still fails, escalate the problem.
PASS If there is a problem with the external device, but the
administered analog line external device alarm, or the
administered Maintenance circuit pack connected to the
device reports no alarm, then the External Device may
not be properly reporting the problems or the External
Device may not be properly connected to the External
Device Alarm Lead.
Table 10-203. TEST #120 External Device Alarm TestContinued
Error
Code
Test
Result Description/ Recommendation
Continued on next page