Page 10-1150PR-MAINT (Maintenance Processor [TN790 RISC Systems])
10
Table 10-342. TEST #229 MTP Auxiliary Loop Around Test
Error
Code
Test
Result Description/ Recommendation
100 ABORT The test did not complete within the allowable time period.
1. Retry the command.
1029
2014
2015
2016
2017
2018
2020
2022
2024
2025
2051
ABORT Refer to STBY-SPE Maintenance documentation for a description of these
error codes.
1000 ABORT The system software resources required for this test are not available.
1. Repeat the command at 1-minute intervals a maximum of 5 times.
1018 ABORT The test has been disabled via administration. The change
system-parameters cdr command needs to administer CDR. (Refer to the
Implementation Manual for more information on administering this port.)
2000 ABORT Response to the test request was not received within the allowable time
period
2033 Internal system error
2034 Port busy
1. Repeat the command at 1-minute intervals a maximum of 5 times.
2500 ABORT The system software resources required for this test are not available.
1. Retry at 1-minute intervals a maximum of 5 times.
1048 ABORT An External Modem is administered to this port.
FAIL The Auxiliary channel failed the Loop Back Test. The AUX port may not be
sending any auxiliary data to the auxiliary collection device.
1. Repeat the command at 1-minute intervals a maximum of 5 times.
2. If test continues to fail, replace the Processor circuit pack.
PASS The Auxiliary channel passed the Loop Back Test. The auxiliary port is
functioning correctly.
1. If no auxiliary data is being recorded, check the auxiliary collection
device, and verify that it has been set up and connected correctly.
Continued on next page