Maintenance Objects 
3-694HYB-LINE (Hybrid Line) 
3
2000 ABORT Response to the test request was not received within the allowable time 
period.
1. Retry the command at 1-minute intervals a maximum of 5 times.
7 FAIL Conference Test failed. User may be able to use conference circuit without 
difficulty in some cases. In other extreme cases, conference calling will be 
totally restricted.
The failure may be due to off-board circumstances, the most common of 
which is an off-hook occurring during the test. Also, check the error logs 
against the GPTD-BD, the TONE-BD, and the TONE-PT.
1. This error can be caused by a disconnected terminal. First, ensure that 
the terminal is connected and the wiring is OK.
2. Then, issue the display port and the status station commands to 
determine if the station is idle. If it is idle, issue the test port command 
for this port.
3. If test continues to fail, issue the busyout port and the release port 
commands, and then retest the port.
4. It is possible that the port may still be functional from a user’s point of 
view.
57 FAIL Hybrid Circuit Test failed. This could result in noisy or bad connections.
1. This error can be caused by a disconnected terminal. First, ensure that 
the terminal is connected and the wiring is OK.
2. Run circuit pack tests to check the Tone Generator circuit pack and 
the Tone Detector circuit pack using the test board PCSS short 
command.
3. Resolve any problems that are detected on the Tone Generator circuit 
pack or Tone Detector circuit pack.
4. If the Tone Generator and Tone Detector circuit packs are functioning 
properly, and the test still fails, replace the Hybrid Line circuit pack.
NOTE:
If the Hybrid Circuit and Conference Circuit Test fails for all ports on 
a circuit pack, a -5 volt power problem is indicated. 
PASS Hybrid Circuit and Conference Circuit Test passed. The hybrid circuitry is 
transmitting properly.
1. If complaints still exist, investigate by using other port tests, and by 
examining the station, wiring, and connections.
Table 3-292. TEST #57 Hybrid Circuit and Conference Circuit Test — Continued
Error 
Code
Te s t 
Result Description/ Recommendation
Continued on next page