User's Manual
DEFINITY ECS Release 8.2 Maintenance for R8.2csi 
555-233-119  Issue 1
April 2000
 Maintenance Objects
3-796MEDPRO (Media Processor MAPD Circuit Pack) 
3
To be fully administered, a MedPro circuit pack must meet 
all of these 4 
conditions
:
1. Have an entry in the circuit pack form (
change circuit pack
)
2. Have the MedPro ip address administered (
change node-names
)
3. Be enabled (
change ip-interface
)
4. Be physically inserted into the correct slot
If the circuit pack has an entry in the circuit packform and either of the 
other two conditions are 
not
 met, a MINOR alarm is logged. To resolve the 
error either
1. Make sure all conditions for administration are met and that a 
functioning MedPro circuit pack is inserted in the correct slot
OR
2. Completely remove the MedPro from the system using the following 
steps:
a. Remove the administered 
IP-Interface associated with the 
circuit pack.
b. Physically remove the circuit pack from the slot.
c. Execute the 
remove medpro UUCSS
 and 
change circuit 
pack UUCSS
 commands.
b.
ErrorType 18
 -The MedPro Interface circuit pack has been busied out by 
a 
busyout board UUCSS
 command.
1. Release the circuit pack (
release board UUCSS
).
c.
Error Type 23
 -The MedPro circuit pack is not completely administered. 
To be fully administered, a MedPro circuit pack must meet 
all of these 4 
conditions
:
1. Have an entry in the circuit plan (
change circuit pack
)
2. Have the MedPro IP address administered (
change node-names
)
3. Be enabled (
change ip-interface
)
4. Be physically inserted into the correct slot.
A DS1 (MEDPRO, MAPD, UDS1-BD and DS1-BD) differs from most circuit 
packs in that inserting the circuit pack into the switch is not enough to 
make the board usable. It must also be administered.
d.
Error Type 125
 - no Aux Data: The wrong circuit pack is inserted in the 
slot where this circuit pack is logically administered. 
1. Remove the wrong circuit pack and insert the logically 
administered circuit pack
OR