1-18Preventive Maintenance Procedures 
1
Preventive Maintenance Procedures
The following preventive maintenance procedures should be followed and 
logged when visiting customer sites:
Preventive Maintenance Log
The sample below shows the DEFINITY Preventive Maintenance Log. Whenever 
you complete any of the preventive maintenance procedures described in this 
section, be sure to fill in the requested information on the log form before leaving 
the customer’s premises.
Air Filters
Air filters should be inspected annually. If a filter is dirty or clogged, first tap it on 
the ground. If the filter is still dirty or clogged, then wash it with warm water and a 
mild detergent. A vacuum cleaner can be used if one is available. If there is no 
facility for washing or vacuuming the air filter, then replace the filter (Comcode 
407745009). Refer to ‘‘Fan and Filter Removal/Replacement’’
 below for more 
information on air filters and fans.
Fan and Filter Removal/Replacement
1. Remove the left door.
2. Remove the fan/filter access panel. See 
Figure 1-3
.
DEFINITY csi Preventive Maintenance Log
Date System Installed: _________________________
Component 
(Comcode)
Scheduled 
Date
Completed 
Date
Completed 
By
Scheduled 
Date
Completed 
Date
Completed 
By
Air Filter
1
(407745009)
1. Inspect annually; see ‘‘Air Filters’’ below for cleaning/replacement details.