Maintenance Objects 
3-266BRI-BD/LGATE-BD (ISDN-BRI Line Circuit Pack) 
3
Table 3-116. TEST #595 LANBIC Receive Parity Error Counter Test 
Error 
Code
Te s t 
Result Description/ Recommendation
2000 ABORT Response to the test was not received from the circuit pack within the 
allowable time period.
1. If the test aborts repeatedly a maximum of 5 times, reset the circuit 
pack via the busyout board PCSS and reset board PCSS 
commands.
2. If the test aborts again, replace the circuit pack.
2100 ABORT Could not allocate the necessary system resources to run this test.
2012 ABORT Internal system error
1. Retry the command at 1-minute intervals a maximum of 5 times.
1-10 FAIL The circuit pack is still detecting errors of this type. The error code 
indicates the value of the on-board error counter.
1. Retry the command at 1-minute intervals a maximum of 5 times.
2. If the test continues to fail, verify the validity of the Packet Bus. Run the 
Packet Bus maintenance test with the test pkt P long command. 
3. If the Packet Bus test passes, check the validity of the circuit pack. 
Execute a test that involves data transmission onto the Packet Bus. For 
example, the BRI may use the connectivity tests of the port-level 
maintenance object (BRI-PORT) by executing the test port PCSSpp 
command. Refer to the repair procedures for the executed test if it 
fails. Otherwise, proceed to the next step.
4. Other circuit packs on the Packet Bus may be the cause of the parity 
error. Use the display errors command to check the Error Log for 
other circuit packs that are alarmed. If any alarms are present for the 
other circuit packs, retire those alarms also. Then, rerun the LANBIC 
Receive Parity Error Counter Test (#595) on this circuit pack.
PASS No errors detected by circuit pack.
Continued on next page