Cut Sheet

CASE TYPE DIMENSIONS
A 6.00 in (152 mm)
B 2.96 in (75 mm)
C 6.73 in (171 mm)
D 6.41 in (163 mm)
(mounting centers)
E 1.58 in (40 mm)
F 0.69 in (18 mm)
G 4.61 in (117 mm)
H 1.43 in (36 mm)
For applications where the Compact SE ballast was flange mounted,
Lutron adapter plate CFL-BEA-BK may be required to retrot the
replacement ballast. Dimensions for the adapter plate are shown below.
8-32 Threaded Stud
0.29 in (7.37 mm)
Adapter Plate
A 4.19 in (106 mm)
B 2.96 in (75 mm)
C 2.04 in (52 mm)
D 1.09 in (28 mm)
E 2.00 in (51 mm)
F 0.52 in (13 mm)
Lutron
® adapter plates CFL-BEA-BK or CFL-JBA-FAB may be required to retrofit replacement ballasts.
The CFL-BEA-BK is used when a non-studded B-can is being replaced by a non-studded K-can. The
CFL-JBA-FAB is used when a studded F-can is being replaced by a studded A-can, B-can or K-can.
Dimensions for the adapter plates are shown below.
Adapter plates Adapter plates
CFL-BEA-BK
CFL-JBA-FAB
* Need to drill new mounting holes in the fixture
Notes
1. When replacing the F-can or B-can with a K-can, it is important to know whether the ballast is mounted by the studs
or the flanges.
2. K-can ballast is wider than the F-can. This may be an issue in narrow fixtures.
3. K-can connector locations don’t exactly match the B-can. They may not line up with fixture mounting plates in
some installations.
K-can Replacement Scenarios for T4 CFL Lamps
Replacement Hardware
Existing installation Sample Model Ballast Can Adapter Plate
F-can with studs FDB-CF18-120-2-B K-can with studs CFL-JBA-FAB
F-can without studs FDB-T418-120-2-E K-can without studs N/A*
B-can with studs FDB-T418-120-2-S K-can with studs N/A
B-can without studs FDB-T418-120-2 K-can without studs CFL-BEA-BK
8-32 Threaded stud
0.29 in (7.37 mm) long
8-32 Threaded stud
0.29 in (7.37 mm) long
Appendix | Discontinued ballasts and drivers Appendix | Discontinued ballasts and drivers
90 | Lutron Lutron | 91