Specification Sheet

Appendix | Wiring diagrams
195
www.lutron.com | 1.800.523.9466 |
Max 0.3A
0-10V
Control Inputs
Load Switched
EARTH/GROUND
CONNECTIONS
L2/H2 100-120
V~
N
2
DL2/DH2
L1/H1
N
1
N
1
SL
1
/SH1
0-10
V
NEUTRAL
L2/H2 220-240
V~
GRX-TVI
L2/H2 100-127
V~
N
2
DL
2
/DH
2
L
1
/H
1
100-277
V~
N
1
N1
SL1/SH1
0-10
V
L
2
/H
2
220-240 V~/CE
EARTH/GROUND
CONNNECTIONS
L2/H2 is the Hot/Live feed that powers
the internal circuitry of the GRX-TVI.
Use L2/H2 100-127
V~ only if your
line/mains voltage is 100-127
V~.
Neutral
Hot Hot
Neutral
Orange
120
VAC
60
Hz Feed
From Distribution
Panel
120/277
VAC
60
Hz Feed
From Distribution
Panel
Green
Red
Neutral
Hot
Wire single-pole,
3-way, or
multi-location
3-wire uorescent
dimmer as normal
except run the
control wire to the
DL2/DH2 terminal.
To Additional
Ballasts
Black
White
Violet (+)
Gray (-)
Black
White
Violet (+)
Gray (-)
0-10
V Control Signal Wires –
DO NOT CONNECT TO LINE VOLTAGE.
Lutron is not liable for damage due
to miswiring.
Dimming Ballast
0-10
V0-10
V
Dimming Ballast
Some 0-10
V LED and uorescent loads require low-end trim adjustments. Select a 3-wire dimmer that has an adjustable low-end trim.
*0-10
VDC sink control
Wiring diagram #42
0-10 V power interface (GRX-TVI) with 3-wire fluorescent dimmer wiring:
0-10 V fluorescent ballast wiring shown