Cut Sheet
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem® Five Control Input Digital Dimming Ballasts
369454k 13  05.27.16
EcoSystem® Ballast Wiring: 
Class 2 Sensors
Electrical Contractors and Engineers:
• Always follow applicable national and local electrical 
code requirements when connecting circuits to 
EcoSystem
® devices
• All field installed Class 2 wiring must be separated 
from line voltage wiring by at least 0.25 in (6.4 mm)
• Some local electrical codes require Class 2 wiring to 
be separately routed in a metal conduit
• Ballast Class 2 Sensor terminals only accept 
22 AWG (0.34 mm
2
) solid conductors; all other 
terminals accept 18 AWG to 16 AWG (0.75 mm
2 
to 
1.5 mm
2
) solid conductors
LutronR Requires:
• Keep Class 1 and Class 2 wiring separate.
• Where separation is not possible, use a 600 V 
insulated cable with an internal shield. Connect the 
shield to ground to provide better noise immunity for 
low voltage circuits
• Refer to Application Note #142 for additional 
information on EcoSystem
® digital link Class 1 and 
Class 2 wiring
Fixture Manufacturers:
• UL
® 1598 6.17.1 allows: 
Factory installed power limited wiring and branch 
circuit wiring that come in random contact within the 
luminaire shall have insulation rated for the maximum 
voltage that exists in any of the circuits. (EcoSystem
® 
ballast circuits require minimum 600 V insulated wire)
• UL
® 1598 6.17.2.1 requires: 
Luminaires designed for the field installation of 
power limited circuits shall be provided with a means 
of segregating or separating the field-installed power 
limited circuit wiring from the branch circuit wiring 
within the luminaire (see UL 1598 6.17 for details)
Lutron Requires:
• Keep Class 1 and Class 2 wiring separate
• Where separation is not possible, use a 600 V 
insulated cable with an internal shield. Connect the 
shield to ground to provide better noise immunity for 
low voltage circuits
13










