Lutron GRX-TVI Power Interfaces
369247e 1 07.07.16
GRX-TVI Ten Volt Interface
Features
• 100-277 V~ forward, reverse, and center phase control
input capability
Provides 0—10 V- control and switching capabilities to
switch and dim current sourcing fluorescent ballasts and
LED drivers.
Switches and dims current sourcing 0—10 V-
electronic dimming ballasts / drivers powered by
100—277 V~. Switches up to 16 A of electronic
capacitive ballasts / drivers.
Switches motors up to 1/2 HP @ 100-120 V~,
1 ½ HP @ 200—277 V~ and 5 A @ 230 V~ CE.
Up to five Ten Volt Interfaces may be connected to one
Control Unit zone. This allows one zone to control up to
five 16 A circuits of Electronic Dimming Ballasts / Drivers
or five motors (This is not true for C5-BMJ-16A).
Provides 100—277 V~ power to loads.
Requires 100—277 V~ power for internal operations.
Compatible Controls
Family Product
Wiring
Diagram
Residential Systems HW-RPM-4U I, J
HW-RPM-4A I, J
HWI-WPM-6D
(Wallbox Power Module)
A, B
HxD-6ND C, D
HWV-FDB-8A E, F
Rx-6ND * C, D
RRD-10ND * C, D
GRX-IA A, B
RRD-6NA * C, D
HQRD-6NA * C, D
HWD-5NE * C, D
Commercial Systems LP-RPM-4U I, J
LP-RPM-4A I, J
GRAFIK Eye
R
Control Unit
3000 Series or
QSG
A, B
GP Panels K, L
C5-BMJ-16A ** M, N
Family Product
Wiring
Diagram
Wallbox Fluorescent
3-wire Dimmers
AYF-103P E, F
DVF-103P E, F
DVSCF-103P E, F
LXF-103PL E, F
MAF-6AM ** G, H
MRF2-F6AN-DV G, H
MSCF-6AM ** G, H
NF-10 E, F
NF-103P E, F
NTF-10 E, F
NTF-103P E, F
SF-10P E, F
SF-103P E, F
VF-10 E, F
VTF-6AM G, H
MRF2-6ELV-120 * C, D
* The low end trim should be set at 28% and the high end trim at
81% manually to have the output signal set to fluorescent load
type.
** These specific controls result in the GRX-TVI not conforming
to the IEC929 standard for 0—10 V- output since they cannot
reach the 1 V- minimum.
All models in this column are set to fluorescent load type except
those model numbers followed by a *.
Note: 277 V~ operation on the control terminal was a design
feature added September 2013. To check whether your TVI has
this feature, please ensure the front label of the TVI shows the
acceptable voltage range as 100—277 V~ for the control input.
Prior revisions of the unit had (2) L2/H2 terminals (one for 120 V~
and one for 240 V~). The current design of the unit accepts a
universal voltage (100—277 V~), so either of these terminals can
be used for the control feed. They are internally tied together.