Cut Sheet

®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247e 12 07.07.16
Wiring Diagram I: HomeWorks® Remote Power Module / LP Module — 1 Distribution Panel / 1 Feed
L2/H2 100-277 V~
GRX-TVI
To additional ballasts / drivers
EARTH / GROUND
CONNECTIONS
Red—Module Output
Switched Line / Hot
Line / Hot
Earth / Ground
Earth / Ground
NOTICE: 0—10 V- Control Signal Wires
— DO NOT CONNECT TO LINE VOLTAGE.
LutronR is not liable for damage due to miswiring.
Use 20 A (10 A CE)
maximum circuit
breaker / MCB
Neutral
White
Black
Distribution
Panel
Neutral
Earth / Ground
Note: Ballast / driver must
provide a 0—10 V- source
only!
RPM / LP
Module
1
Terminal
Blocks
L2 / H2 terminals are tied to each other
internally. It is the Line / Hot feed that
powers the internal circuitry of the
GRX-TVI. Use the appropriate voltage
in the range of 100277 V~. Refer to
the Note on the first page of the
GRX-TVI Specification Submittal.
L1 / H1 is the Line / Hot feed that
powers the Switched Line / Hot
output to the load. Shown in
picture as the same voltage as
L2 / H2.
Neutral
Line / Mains Voltage:
100—240 V~
0—10 V-
Ballast / Driver
1
0—10 V-
Ballast / Driver
1
1
Remote Power Modules and ballasts / drivers must be rated for the specific Line / Mains
voltage utilized.
Wiring Diagrams (continu ed)
12