Lutron GRX-TVI Power Interfaces
369247e 13 07.07.16
L2/H2 100-277 V~
Wiring Diagram J: HomeWorks® Remote Power Module / LP Module — 2 Distribution Panels / 2 Feeds
Line / Hot
Neutral (white wire)
Earth / Ground
Distribution
Panel B
Distribution
Panel A
GRX-TVI
To additional ballasts / drivers
EARTH / GROUND
CONNECTIONS
Red—Module Output
Switched Line / Hot
Line / Hot
Earth / Ground
Earth / Ground
NOTICE: 0
10 V- Control Signal Wires
— DO NOT CONNECT TO LINE VOLTAGE.
LutronR is not liable for damage due to miswiring.
Use 20 A (10 A CE)
maximum circuit
breaker / MCB
Neutral
White
Black
Neutral
Earth / Ground
Note: Ballast / driver must
provide a 0—10 V- source
only!
RPM / LP
Module
1
Terminal
Blocks
L2 / H2 terminals are tied to each other
internally. It is the Line / Hot feed that
powers the internal circuitry of the
GRX-TVI. Use the appropriate voltage
in the range of 100277 V~. Refer to
the Note on the first page of the
GRX-TVI Specification Submittal.
L1 / H1 is the Line / Hot feed that
powers the Switched Line / Hot
output to the load. Use any voltage
in the range of 100277 V~.
Note: If the voltage of the ballast / driver is
different from the voltage of the control device,
they should come from different distribution panels
(demonstrated above).
If the control side plus the load side current is
greater than the circuit breaker rating, and the
voltages of load and control are the same level,
follow Diagram O.
Line / Mains Voltage:
100277 V~
0—10 V-
Ballast / Driver
2
0—10 V-
Ballast / Driver
2
1
Remote Power Module must be rated for the Distribution Panel A Line / Mains voltage utilized.
2
Ballasts / drivers must be rated for the Distribution Panel B Line / Mains voltage utilized.
Line / Mains Voltage:
100240 V~
Wiring Diagrams (continu ed)