Cut Sheet

®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247e 15 07.07.16
L2/H2 100-277 V~
Wiring Diagram L: GP Panel — 2 Distribution Panels / 2 Feeds
Use 20 A (10 A CE)
maximum circuit
breaker / MCB
Distribution
Panel B
GRX-TVI
To additional ballasts / drivers
EARTH / GROUND
CONNECTIONS
Switched Line / Hot
Line / Hot
Dimmed Line /
Dimmed Hot, DL / DH
Earth / Ground
Earth / Ground
NOTICE: 0—10 V- Control Signal Wires
— DO NOT CONNECT TO LINE VOLTAGE.
LutronR is not liable for damage due to miswiring.
Neutral
Neutral
Earth / Ground
Note: Ballast / driver must
provide a 0—10 V- source
only!
GP Panel
1
Load
Terminals
(1 circuit
shown)
Line / Hot
Neutral
Earth / Ground
L2 / H2 terminals are tied to each other
internally. It is the Line / Hot feed that
powers the internal circuitry of the
GRX-TVI. Use the appropriate voltage
in the range of 100277 V~. Refer to
the Note on the first page of the
GRX-TVI Specification Submittal.
L1 / H1 is the Line / Hot feed that
powers the Switched Line / Hot
output to the load. Use any voltage
in the range of 100277 V~.
Line / Mains Voltage:
100—277 V~
0—10 V-
Ballast / Driver
2
0—10 V-
Ballast / Driver
2
1
GP Panel must be rated for the for the specific Line / Mains voltage utilized.
2
Ballasts / drivers must be rated for the Distribution Panel B Line / Mains voltage utilized.