Cut Sheet
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247e 17 07.07.16
Wiring Diagram N: EcoSystemR Dimming Power Module for 3-wire LutronR Dimming Ballast / drivers
— 2 Distribution Panels / 2 Feeds
L2/H2 100-277 V~
E1
E1
+20V
Common
IR
OCC
Daylight
E2
E2
Class 2 Sensors
Capteurs Classe 2
Sensores Clase 2
Class 2 Link
Lien Classe 2
Enlace Clase 2
EcoSystem
®
Multiple Fixture Dimming Control
Contrôle de gradation de multiples luminaires
Control atenuador de múltiples lámparas
PWR
STAT
Indicateur de puissance (PWR)
On: l’unité est alimentée
Off: l’unité n’est pas alimentée
ou est dysfonctionnelle
Indicateur d’activité (STAT)
Plein: Niveau de circuit
Impulsion: Aucune
communication
Power Indicator (PWR)
On: Unit is powered
Off: Unit is not powered
or is malfunctioning
Status Indicator (STAT)
Solid: Circuit Level
Pulse: No communication
Indicador de Alimentación (PWR)
Encendido: unidad tiene corriente
Apagado: unidad no tiene corriente
o no está funcionando correctamente
Indicador de estado (STAT)
Sólido: Nivel del Circuito
Pulsante: No hay comunicación
C5-BMJ-16A
COM
DYLT
P/N 500-10755
®
GRX-TVI
EcoSystemR
Power
Module
2
To additional ballasts / drivers
EARTH / GROUND
CONNECTIONS
Red
1
Black
Switched Line / Hot
Line / Hot
Earth / Ground
Earth / Ground
NOTICE: 0—10 V- Control Signal Wires
— DO NOT CONNECT TO LINE VOLTAGE.
LutronR is not liable for damage due to miswiring.
Use 20 A (10 A CE)
maximum circuit
breaker / MCB
White
Orange
Distribution
Panel A
Neutral
Earth / Ground
Note: Ballast / driver must
provide a 0—10 V- source
only!
L2 / H2 terminals are tied to each other
internally. It is the Line / Hot feed that
powers the internal circuitry of the
GRX-TVI. Use the appropriate voltage in
the range of 100—277 V~. Refer to the
Note on the first page of the GRX-TVI
Specification Submittal.
L1 / H1 is the Line / Hot feed that
powers the Switched Line / Hot
output to the load. Use any voltage
in the range of 100—277 V~.
Neutral
Green
E1
E2
To additional
EcoSystemR
modules,
ballast / drivers
and EcoSystemR
Bus Supply
Distribution
Panel B
Line / Hot
Earth / Ground
Neutral
Note: If the voltage of the ballast / driver is
different from the voltage of the control device,
they should come from different distribution panels
(demonstrated above).
If the control side plus the load side current is
greater than the circuit breaker rating, and the
voltages of load and control are the same level,
follow Diagram O.
Line / Mains Voltage:
100—277 V~
Use 20 A (10 A CE)
maximum circuit
breaker / MCB
0—10 V-
Ballast / Driver
3
0—10 V-
Ballast / Driver
3
1
The red wire is not used. Cap off the red wire using a wire connector. Do not wire the red wire to
ground or to any other wiring.
2
The EcoSystem Power Module must be rated for the for the Distribution Panel A Line / Mains
voltage utilized.
3
Ballasts / drivers must be rated for the Distribution Panel B Line / Mains voltage utilized.
17