Cut Sheet
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247e 18 07.07.16
Wiring Diagram O: 1 Distribution Panel with 2 Separate Feeds
N2
N1
L2/H2 100-277 V~
GRX-TVI
Remote
Dimmer
1
Dimmer
1
To additional ballasts / drivers
EARTH / GROUND
CONNECTIONS
BlueBrass
Black
BlueBrass
Silver
Black
Switched Line / Hot
Line / Hot 1
Line / Hot 2
Earth / Ground
Earth / Ground
NOTICE: 0—10 V- Control Signal Wires
— DO NOT CONNECT TO LINE VOLTAGE.
LutronR is not liable for damage due to miswiring.
Use 20 A (10 A CE)
maximum circuit
breaker / MCB
Neutral
Neutral
Note: Ballast / driver must
provide a 0—10 V- source
only!
Line / Hot
Neutral 1
Distribution
Panel
Earth / Ground
Note: Dimmer
must be wired
on the load
side.
L2 / H2 terminals are tied to each
other internally. It is the Line / Hot
feed that powers the internal circuitry
of the GRX-TVI. Use the appropriate
voltage in the range of 100—277 V~.
Refer to the Note on the first page of
the GRX-TVI Specification Submittal.
L1 / H1 is the Line / Hot feed that
powers the Switched Line / Hot
output to the load.
Use any voltage in the range of
100—277 V~. Shown in picture as
the same voltage as L2 / H2.
Neutral 2
Note: Wiring of the dimmer could vary depending
on the type of dimmer that you choose. Consult
Lutron at 1.800.523.9466 or www.lutron.com.
Line / Mains Voltage:
100—277 V~
0—10 V-
Ballast / Driver
1
0—10 V-
Ballast / Driver
1
1
Dimmers and ballasts / drivers must be rated for the specific Line / Mains voltage utilized.
18