Cut Sheet
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247e 2 07.07.16
Specifications
Regulatory Approvals
• cUL
® Listed in US and Canada
• CE
• NOM (Mexico)
• Complies with requirements for use in other spaces
used for environmental air (plenums) per
NEC
® 2014 300.22(C)(3)
• Meets the Canadian National Building Code plenum
requirements for a concealed space used as a
plenum within a floor or roof assembly
Power
• Control circuit: 100—277 V~
• Output/Load circuit: 100—277 V~
• Control and Load circuits are independent of each
other and can have unique phases
• Works with all ballasts and drivers that provide a
current source that is compliant to IEC 60629 Annex
E.2, and whose inrush current does not exceed
NEMA410 standards for electronic ballast/driver
0-10 V- Dimming Control
• Output rating: 10 μA—300 mA. Sinks current only
(ballast / driver must source / provide 10 V- supply).
<1 V- minimum, >10 V- maximum
Zone Capacity
• Up to five Ten Volt Interfaces per Control Unit zone.
(This is not true for C5-BMJ-16A)
Key Design Features
• Complies with UL508 Standard
• Provides a Class 2 isolated 0—10 V- output signal
that conforms to EN60929 and IEC929
• Accepts a forward, reverse and center phase control
signal (100—277V~ 50 / 60 Hz)
Terminals
• Each terminal accepts up to two 12 AWG (2.5 mm
2
)
conductors
Physical Design
• Wall-mounted. Indoor use only. Type 1 enclosure.
• Weight: 4.25 lbs (2 kg)
Environment
• Temperature: 32 ºF to 104 ºF (0 ºC to 40 ºC)
• 0 to 90% humidity, non-condensing
Switching Load Types and Capacities
Source / Load Type 100—277 V~ * 230 V~ (CE)
Fluorescent
• Electronic Capacitive
Non-Dim
• Other manufacturers'
0—10 V- ballasts / drivers
16 A
16 A
10 A
10 A
LED 16 A 10 A
Incandescent 16 A 10 A
Low-voltage 16 A 10 A
Metal Halide 16 A 10 A
Neon / Cold Cathode 16 A 10 A
Motor 1/2 HP @ 100—120 V~
1 ½ HP @ 200—277 V~
5 A @ 230 V~ CE
* Not if product requires CE certification
2










