Cut Sheet
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247e 6 07.07.16
Wiring Diagram C: HomeWorks® MaestroR / RadioRAR / RadioRA® 2 Dimmers
— 1 Distribution Panel / 1 Feed
L2/H2 100-277 V~
GRX-TVI
Remote
Dimmer
1
Dimmer
1
To additional ballast / drivers
EARTH / GROUND
CONNECTIONS
Blue
2
Brass
Black
Blue
2
Brass
Silver
Black
Switched Line / Hot
Line / Hot
Line / Hot
Earth / Ground
Earth / Ground
NOTICE: 0—10 V- Control Signal Wires
— DO NOT CONNECT TO LINE VOLTAGE.
LutronR is not liable for damage due to miswiring.
Use 20 A (10 A CE)
maximum circuit
breaker / MCB
Neutral
Neutral
(white wire)
Distribution
Panel
Neutral (white wire)
Earth / Ground
Note: Ballast / Driver must
provide a 0—10 V- source
only!
Note: Dimmer
must be wired on
the load side of the
Remote Dimmer.
L2 / H2 terminals are tied to each other
internally. It is the Line / Hot feed that
powers the internal circuitry of the
GRX-TVI. Use the appropriate voltage in
the range of 100—277 V~. Refer to the
Note on the first page of the
GRX-TVI Specification Submittal.
L1 / H1 is the Line / Hot feed that powers
the Switched Line / Hot output to the
load. Shown in picture as the same
voltage as L2 / H2.
Neutral
Line / Mains Voltage:
100—240 V~
2
When used as a single-pole dimmer, the blue screw terminal is not used.
Tighten the blue screw terminal—do not connect the blue screw terminal to
ground or to any other wiring.
0—10 V-
Ballast / Driver
1
0—10 V-
Ballast / Driver
1
1
Dimmers and ballasts / drivers must be rated for the specific Line / Mains voltage
utilized.
Wiring Diagrams (continu ed)
6