Cut Sheet

®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247e 9 07.07.16
Wiring Diagram F: AriadniR / DivaR / LyneoR / SkylarkR / NovaR / Nova T R / VareoR 3-wire Fluorescent Dimmers
— 2 Distribution Panels / 2 Feeds
L2/H2 100-277 V~
Line / Hot
Neutral
Earth / Ground
Distribution
Panel B
GRX-TVI
3-way
Switch
1
To additional ballasts / drivers
EARTH / GROUND
CONNECTIONS
Red
4
Blue
3
Brass /
Gold
Copper /
Black
Copper /
Black
Violet
or Blue
Switched Line / Hot
Line / Hot
Earth / Ground
Earth / Ground
NOTICE: 0—10 V- Control Signal Wires
— DO NOT CONNECT TO LINE VOLTAGE.
LutronR is not liable for damage due
to miswiring.
Use 20 A (10 A CE)
maximum circuit
breaker / MCB
Neutral
White
Yellow or
Orange
Distribution
Panel A
Neutral
Earth / Ground
Note: Ballast / driver must
provide a 0—10 V- source
only!
L2 / H2 terminals are tied to each other
internally. It is the Line / Hot feed that
powers the internal circuitry of the
GRX-TVI. Use the appropriate voltage in
the range of 100277 V~. Refer to the
Note on the first page of the GRX-TVI
Specification Submittal.
L1 / H1 is the Line / Hot feed that
powers the Switched Line / Hot
output to the load. Use any
voltage in the range of
100277 V~.
Note: If the voltage of the ballast / driver is
different from the voltage of the control device,
they should come from different distribution panels
(demonstrated above).
If the control side plus the load side current is
greater than the circuit breaker rating, and the
voltages of load and control are the same level,
follow Diagram O.
Line / Mains Voltage:
100—277 V~
0—10 V-
Ballast / Driver
2
0—10 V-
Ballast / Driver
2
1
Switches and dimmers must be rated for the Distribution Panel A Line / Mains
voltage utilized.
2
Ballasts / drivers must be rated for the Distribution Panel B Line / Mains
voltage utilized.
3
Single pole dimmers use black for the line / hot wire. Refer to the single-pole
dimmer's installation instructions to identify the line / hot wire for that product.
4
The red wire is not used. Cap off the red wire using a wire connector. Do not wire
the red wire to ground or to any other wiring.
Dimmer
1
Line / Mains Voltage:
100—277 V~
Wiring Diagrams (continu ed)
9