Cut Sheet
Table Of Contents
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive HJS-0, HJS-1, HJS-2 Wireless Hub
369902d 3 06.16.17
Specifications
Regulatory Approvals
•cULus® Listed
•FCCapproved.ComplieswiththelimitsforaClassB
device, pursuant to Part 15 of the FCC rules.
•IC
•ComplieswithCOFETELrequirements
•ComplieswithNOM-001
Power / Performance
•Inputtopowersupply:
120 – 277 V~
50 / 60 Hz
0.6 A
•InputtoVivehub:
24 V-
350 mA
System Limits
•HJS-1,HJS-2supportupto700LutronWireless
devices.HJS-0limitedto75devices.Devicesmustbe
located within 71 ft (22 m) of the Vive hub.
•Anygivenloaddevicecanbecontrolledby
10 occupancy sensors, 10 Pico remote controls and
1 daylight sensor (Pico remote controls and sensors
must be located within 30 ft [9 m] of the load device
they are controlling).
Mounting
•Vivehubunitsshouldbemountedinthemiddleof
non-metal ceiling tile or drywall, visible from inside the
space.
•Installationnearmetal,otherthanajunctionbox,
may reduce RF range. Hub should be at least 12 in
(305mm)awayfrommetalobjects.
•Usesurface-mountversionformountingtoahard
or cement ceiling.
•Powersupplymountstoastandard4inx4in
(101mmx101mm)squarejunctionbox.
•Powersupplymustbemountedwithin100ft(31m)of
the Vive hub. Wiring should be 24 AWG to
12 AWG (0.2 mm
2
to 2.5 mm
2
).
Environment
•Forindooruseonly.
•32to104°F(0to40°C).
•Relativehumiditylessthan90%non-condensing.
Contact Closure Input Terminals
•Onlytherstcontactclosureisused.
•Acceptsonlymaintainedinputs.
•Off-stateleakagecurrentmustbelessthan100μA.
•Opencircuitvoltage:24V- maximum.
•Inputwiring:24AWGto12AWG(0.2mm
2
to 2.5 mm
2
).
•ContactClosureInputsonmultiplehubscanbe
wired in parallel. DO NOT wire inputs in parallel
with other equipment as it can cause the inputs
on either of the devices to falsely trigger.
•Upto4hubsinparallel.
•ToensureproperoperationofContactClosure
Inputs,aPS-J-20W-UNVpowersupplymaynot
be used to provide power to more than one hub.
•Inputsmustbedrycontactclosure,solidstate,
open collector, or active-low (NPN) / active high
(PNP) output.
- Open collector NPN or active-low on-state voltage
must be less than 2 V and sink 3.0 mA.
- Open collector PNP or active-high on-state voltage
must be greater than 12 V and source 3.0 mA.
Additional Software Features
•MeasuredenergydataforPowPakWireless
FixtureControlaccurateto±2%,or0.5W,
whichever is higher.
•CalculatedenergydataforPowPakmodulesand
Maestrodimmersorswitchesat10%accuracy.
•Createandeditareas.
•Tunearealightlevelsbytrimmingthehigh-endand
low-end output to save energy.
•Adjustoccupancysettings.Createoccupancy
groups.
•Loadshediscongurable.
Warranty
•1yearlimitedwarranty.Thecustomercanregister
the product to increase the warranty period from
1 year to 5 years. Please visit www.lutron.com/
TechnicalDocumentLibrary/369-119_Wallbox_
Warranty.pdf for warranty details.
3