Cut Sheet
Shown above: EcoSystem H-Series, M-case
Model numbers are organized by lamp type, refer to pg. 41 for additional information.
Features
•
Continuous, flicker-free dimming down to 0.7% or
1% of full light output for T8 lamps, 1% for T5 and
T5 HO lamps
•
The EcoSystem digital link allows for re-zoning
without rewiring, and can be wired as Class 1 or
Class 2—perfect for retrofit and new construction
•
The EcoSystem digital link supports up to 64
digital ballasts, 64 occupancy sensors, 16 daylight
sensors, and 64 wallstations or IR receivers
•
The PowPakTM dimming module with EcoSystem
supports 32 EcoSystem ballasts or drivers,
9 Pico
® wireless controls, 6 occupancy/vacancy
sensors and 1 daylight sensor
•
Low-voltage, 2-conductor EcoSystem digital link
provides individual, reconfigurable fixture control
•
Sensors cannot connect directly to EcoSystem
H-Series ballasts
•
Communicates with wired or wireless sensors and
controls via compatible device
•
Line-voltage miswire protection of EcoSystem link
•
Slim-profile design
•
Ballasts maintain consistent light output for different
lamp lengths, ensuring fixture-to-fixture uniformity
•
Lamps turn on at any dimmed level without going
to full brightness
•
100% performance-tested, including burn-in at
the factory
Mounting
•
Ballast mounts using two screws (or sheet metal
feature and one screw) within a fluorescent fixture
•
Ballast is grounded via a mounting screw to thefixture
•
Lutron® and NEMA® recommend sockets
complying with IEC 60400. Sockets must have
a UL mark as well. Use rapid start sockets, not
instant startsockets.
•
Terminals accept 16-18 AWG (0.75 to 1.5 mm
2
)
solid copper or tinned stranded wire
EcoSystem H-Series digitally addressable ballasts offer a low-cost, flexible solution for any space
in an application. Providing industry-leading dimming to 1% or less, they meet the needs of the
most demanding applications. The EcoSystem digital link also provides individual control, which
eliminates the need to rewire, reduces design time, and provides a scalable solution from a small
area to an entire building.
Highest performance dimming to 1% at a low cost
EcoSystem digital link controlled
Operating voltage
•
Universal input (120 V, 220/240 V and 277 V
@ 50/60 Hz) and 347 V @ 60 Hz
Lamp types and wattages
UL Listed (for North America):
•
T8 linear and U-bent: 17 W, 25 W, 32 W
•
T5 HO linear: 24 W, 39 W, 54 W
•
T5 linear: 14 W, 21 W, 28 W
Global models:
•
T8 linear: 32 W
•
T5 HO linear: 24 W, 39 W, 54 W
•
T5 linear: 14 W, 21 W, 28 W
Control option
•
EcoSystem digital link
Available case types
•
G-case
•
M-case
•
C-case (347 V only)
Key standards
•
California Energy Commission Listed
•
UL Listed (evaluated to the requirements
of UL 935)
•
CSA Certified (evaluated to the requirements
of C22.2 No. 74)
•
Meets FCC Part 18 Non-Consumer requirements
for EMI/RFI emissions
•
Select models are NOM listed
•
Models are also available to meet global country-
specific standards. See pg. 60 for a listing of global
model numbers
For system compatibility information, see pg. 12.
CE, CSA, CCC AND INMETRO
MODELS AVAILABLE
Specifications
•
Total Harmonic Distortion (THD): less than 10%
•
Power factor greater than 0.95
•
Ballast factor equal to 1.0 or 1.17 for T8 lamps
•
Ballast factor equal to 1.0 for T5 and T5 HO lamps
and all international models
•
Non-volatile memory restores all ballast settings
after power failure
•
Frequency of operation greater than 42 kHz
•
Built-in inrush current-limiting circuitry (maximum
of 7 amps at 120 V and 3 amps at 277 V)
•
Factory-tuned ballast factors available to
customize the ballast for different applications
(not available for models outside the US)
Environment
•
Sound rating: Class A
•
Minimum lamp starting temperature 10º C (50º F)
•
Maximum ballast case temperature 75º C (167º F)
Wiring
•
EcoSystem H-Series ballasts require 4 wires plus
Ground (E1, E2, Constant Hot and Neutral); one
16-18 AWG solid copper Class 1 or Class 2 wire
per terminal
•
The 16 AWG control wire must not exceed 900 ft,
and the 18 AWG must not exceed 550 ft; maximum
ballast-to-lamp-socket lead length is 7 ft (2 m) for
T8, T5 and T5 HO linear lamps
•
For control wiring diagrams, see pg. 68, and for
lamp wiring diagrams, see pg. 78