Cut Sheet

Available case types
C-case
G-case
Key standards
California Energy Commission Listed
UL Listed (evaluated to the requirements of UL 935)
CSA certified (evaluated to the requirements of
C22.2 No. 74, specific model numbers only)
Meets FCC Part 18 Non-Consumer requirements
for EMI/RFI emissions
Select models are NOM listed
Shown above: Hi-lume 3D, G-case
Model numbers are organized by lamp type, refer to pg. 41 for additional information.
Operating voltage
Universal input
(120 V, 220/240 V, 277 V @ 50/60 Hz)
Lamp types and wattages
T8 linear and U-bent: 17 W, 25 W, 32 W, 40 W
T5 HO linear: 24 W, 39 W, 54 W, 80 W
1
T5 linear: 14 W, 21 W, 28 W
T5 twin tube
1
: 36 W, 40 W, 50 W
Control options
EcoSystem digital link
3-Wire control
Hi-lume 3D is a high-performance, energy-efficient, digitally addressable dimming ballast for
demanding architectural applications. Hi-lume 3D is the world’s first fluorescent dimming ballast
that dims lights to 1% or less for T8 lamps. With Hi-lume 3D you get the highest performance
fluorescent dimming with the same efficiency as non-dimmable ballasts.
Highest performance dimming to 1%
EcoSystem® digital link or 3-wire controlled
Environment
Sound rating: Class A
Minimum lamp starting temperature 10º C (50º F)
Maximum ballast case temperature 75º C (167º F)
Mounting
Ballast mounts using two screws (or sheet metal
feature and one screw) within a fluorescent fixture
Ballast is grounded via a mounting screw to
the fixture
Lutron and NEMA® recommend sockets complying
with IEC 60400. Sockets must have a UL mark
as well. Use rapid start sockets, not instant
startsockets.
Terminals accept 16-18 AWG (0.75 to 1.5 mm
2
)
solid copper or tinned stranded wire
Wiring
EcoSystem digital link: Hi-lume 3D ballasts
require 4 wires plus Ground (E1, E2, Constant Hot
and Neutral); one 16-18 AWG solid copper Class 1
or Class 2 wire per terminal
3-Wire: Hi-lume 3D ballasts require 3 wires
plus Ground (Dimmed Hot, Switched Hot and
Neutral); one 16-18 AWG solid copper Class 1 wire
perterminal
The 16 AWG control wire must not exceed 900 ft,
and the 18 AWG must not exceed 550 ft; maximum
ballast-to-lamp-socket lead length is 7 ft (2 m) for
T8, T5 and T5 HO linear lamps, and 3 ft (1 m) for T5
twin-tube lamps
Ballast is grounded via case
For control wiring diagrams, see pg. 68, and for
lamp wiring diagrams, see pg. 78.
Features
Industry-leading ballast efficacy of up to 100
lumens per watt
Broadest dimming range: continuous, flicker-free
dimming down to 0.7% of full light output for T8
lamps, 1% for T5 and T5 HO lamps, and 5% for
T5 twin-tube and T5 HO 80 W lamps
The EcoSystem digital link supports up to 64
digital ballasts, 64 occupancy sensors, 16 daylight
sensors, and 64 wallstations or IR receivers
The PowPakTM dimming module with EcoSystem
supports 32 EcoSystem ballasts or drivers,
9 Pico
® wireless controls, 6 occupancy/vacancy
sensors and 1 daylight sensor
EcoSystem digital link allows for re-zoning without
rewiring, and can be wired as Class 1 or Class 2—
perfect for retrofit and new construction
Sensors cannot connect directly to the
Hi-lume 3D ballasts
Communicates with wired or wireless sensors and
controls via compatible device
Line-voltage miswire protection of EcoSystem link
Slim-profile design
Ballasts maintain consistent light output for different
lamp lengths, ensuring fixture-to-fixture uniformity
Lamps turn on at any dimmed level without going
to full brightness
100% performance-tested, including burn-in at
the factory
Specifications
Total Harmonic Distortion (THD): less than 10%
Power factor greater than .95
Ballast factor equal to 1.0 or 1.17 for T8 lamps
Ballast factor equal to 1.0 for T5 lamps
Frequency of operation greater than 42 kHz
Factory-tuned ballast factors available to customize
the ballast for different applications
For system compatibility information, see pg. 12.
1
80 W T5 HO model and T5 twin-tube models dim to 5%