Operating Voltage
•
220–240 V CE @ 50/60 Hz
Control options
•
EcoSystem digital link
Lamp types and wattages
•
LED light engines, up to 25 W
Available case types
•
P-case
Shown above: EcoSystem LED driver, P-case
Model number is determined by load and control type. See pg. 64 for additional information.
Providing smooth and continuous 1% dimming, the high-performance EcoSystem LED driver works
with virtually any LED fixture. It communicates via the EcoSystem digital link, a revolutionary technology
that allows the driver to react to its environment. It also allows for individual control of the drivers, which
eliminates the need to rewire, and provides a scalable solution for almost any application. The EcoSystem
LED driver is available for fixtures requiring either constant current or constant voltage.
LED operating specifications
Constant Current
•
0.20 A–1.05 A (in 0.01 A increments)
•
5 W–25 W
•
Pulse width modulation (PWM) or constant current
reduction (CCR) dimming
Constant Voltage
•
8 V–38 V (in 0.5 V increments)
•
5 W–25 W
•
Pulse width modulation (PWM) dimming
Highest performance dimming to 1%
EcoSystem digital link controlled
Key standards
•
CE and ENEC Mark
•
RoHS 2006 Compliant
•
IEC Rated
Features
•
Continuous, flicker-free dimming from
100% to 1%
•
Efficiency of 80% at 25 W
•
Protected from miswires of input power to
EcoSystem control inputs
•
Constant current reduction (CCR) and pulse
width modulation (PWM) dimming available for
constant current light engines; constant voltage
light engines operate with pulse width modulation
(PWM) dimming only
•
A rated lifetime of 50,000 hours
•
Independent control gear with integral strain relief
•
LEDs turn on to any dimmed level without flashing
to full brightness
•
Sensors cannot connect directly to the driver
For system compatibility information, see pg. 12.
Specifications
•
Power factor greater than 0.95 at 25 W
•
Low harmonic distortion
•
Inrush current less than 2 A
Environment
•
Sound rating: inaudible in a 27 dB
ambientenvironment
Mounting
•
Independent control gear, driver requires
noparticular mounting means
Wiring
•
EcoSystem LED drivers require 4 wires plus
Ground (E1, E2, Live and Neutral); one 0.75 mm
2
to 1.5 mm
2
solid copper Class 1 or Class 2 wire
perterminal
•
The 1.5 mm
2
control wire must not exceed
310 m, and the 0.75 mm
2
must not exceed 50 m;
maximum driver-to-LED light engine wire length
is 3 m for any output type
•
For control wiring diagrams, see pg. 75, and for
lamp wiring diagrams, see pg. 80.
CE MODELS ONLY
Ballasts and drivers | Ballasts and drivers |
38 | Lutron Lutron | 39
EcoSystem® LED drivers EcoSystem LED drivers