Cut Sheet

Details for building a Lutron® LED driver model number
For more information, please use the following resources:
LED Driver Selection Tool (www.lutron.com/LEDBuildAModel)
Lutron LED Control Center of Excellence (1-877-DIM-LED8 or email LEDs@lutron.com)
Control type
Features Ideal applications
2-Wire forward
phase control
Typically used for incandescent and
MLV light sources
Generally the only control used for LED
retrofit lamps
Most common method of dimming control
Retrofit projects
Residential and
commercial system
applications
Applications that
have a neutral wire
in the backbox
EcoSystem digital
link control
Digitally addressable and allows LED drivers to
communicate and react to environmental changes
Allows for rezoning without rewiring, and all links
are miswire protected
Projects requiring digital
control for individual
fixture addressability
Upgrade from analog
0-10 V control
Multi-zone applications
Small, retrofit
applications using
Lutron Energi TriPak
TM
3-Wire control
Requires a third line voltage control wire,
resulting in more precise performance and less
electrical noise
Stable over long wire runs
Easily wired
LED dimming
applications requiring
precise control
1
2
Choosing a control type input
The following control technologies refer to the signal and wiring between the control on the wall and the
LED driver. The compatibility of a dimmer with a particular LED fixture begins with making sure they both
use the same control method. These control technologies are used in standalone applications and control
systems as well as in wired and wireless lighting controls.
Selection of a control is typically driven by the requirements of the project.
1
How to build an EcoSystem® LED model number (CE models):
L DE A2E1C PA – __ __ __ __ __
Control type:*
DE = Digital Only
EcoSystem
Constant voltage
A = 8.0 V–12.0 V
B = 12.5 V–20.0 V
C = 20.5 V–24.0 V
D = 24.5 V–40.0 V
1.05 A and 25 W maximum
Constant current
G = 0.20 A–0.70 A 8 V–20 V
H = 0.20 A–0.70 A 15 V–40 V
I = 0.71 A–1.05 A 8 V–20 V
J = 0.71 A–1.05 A 15 V–40 V
40 V and 25 W maximum
LED load output range (see following
pages for explanation and examples):
1
Driver output:*
C = Constant current driver with pulse
width modulation (PWM) dimming
A = Constant current driver with constant
current reduction (CCR) dimming
V = Constant voltage driver with pulse
width modulation (PWM) dimming
Current level (for constant current):*
020 = 0.20 A; 021 = 0.21 A … 105 = 1.05 A
Voltage level (for constant voltage):*
100 = 10.0 V; 105 = 10.5 V … 400 = 40.0 V
2
LED
*
For details on control types, see pg. 65
For current/voltage level and driver output information, see pgs. 66 and 67.
Ballasts and drivers | Ballasts and drivers |
64 | Lutron Lutron | 65
LED driver model numbers
LED driver model numbers