The EcoSystem digital link and power terminals
only accept one 16-18 AWG (0.75 mm
2
-1.5 mm
2
)
solid copper wire per terminal (12–14 AWG wires
require a wire nut to connect to terminal)
Ballasts, drivers and lighting fixtures must be
effectivelygrounded
Ballasts and drivers must be installed per national
and local electrical codes
Driver is grounded by a mounting screw to the
grounded fixture (or by terminal connection on
the K-case)
Control wiring overview
The EcoSystem digital link (E1 and E2) connects
the digital ballasts or drivers together to form a
lighting control system
Control wires (E1 and E2) are not polarity sensitive
and can be wired in any topology
The EcoSystem digital control device does not
have to be located at the end of the digital link
The EcoSystem digital link supports up to
64 digital ballasts or drivers, 64 occupant sensors,
16 daylight sensors, and 64 wallstations or
IR receivers
The PowPakTM dimming module with EcoSystem
supports 32 EcoSystem ballasts or drivers,
9 Pico
® wireless controls, 6 occupancy/vacancy
sensors and 1 daylight sensor
Control wire colors may not match ballast or driver
wire colors
Features
1
Power and digital link
terminals accept only
one 16-18 AWG
(0.75 to 1.5 mm
2
) wire
2
See charts on pg. 69 for
EcoSystem digital link wiring
length details
* The Constant Hot must not be wired to a switching device when using EcoSystem control.
** Ballast is grounded via case.
Wire gauge Digital link length (max)
12 AWG 2200 ft (670 m)
14 AWG 1400 ft (430 m)
16 AWG 900 ft (275 m)
18 AWG 550 ft (170 m)
Wire size Digital link length (max)
4.0 mm
2
830 m
2.5 mm
2
520 m
1.5 mm
2
310 m
1.0 mm
2
210 m
0.75 mm
2
155 m
EcoSystem digital link length is limited by the
wire gauge used for control wires as follows:
(Use for North America)
(Use outside of North America)
E1
E2
NEU
HOT
N/C
Class 2
Bus
LINE
Ballast
or
Driver
E1
Neutral
Constant Hot*
E2
Ground**
EcoSystem digital link control, C-case, J-case or M-case
2 1
E1
E2
NEU
HOT
N/C
Class 2
Bus
LINE
Ballast
E1
Neutral
Constant Hot*
E2
Ground**
N/C or
sensors
EcoSystem digital link control, G-case
2 1
EcoSystem® digital link control
Ground
HOT
NEU
DH
Ballast
or
Driver
GND
E1
E2
LINE
Class 2
Bus
E1
Neutral
Constant Hot*
E2
EcoSystem digital link control, K-case
(View from bottom)
2
1
Terminals may be
located on side
and bottom.
K-case can be
grounded via case
or ground terminal.