Cut Sheet
Control wiring overview
•
Class 2 must be separated from Class 1 and line
voltage wiring by 0.25 in (6 mm) or a physical barrier
•
Sensors cannot connect directly to the ballast
or driver
•
Control wire colors may not match ballast or driver
wire colors
Technical wiring details
•
Power input terminals only accept one 16-18 AWG
or 0.75 mm
2
-1.5 mm
2
solid copper wire per terminal
•
Ballasts, drivers and lighting fixtures must be
effectively grounded
•
Ballasts and drivers must be installed per national
and local electrical codes
E1
E2
NEU
HOT
DH
Class 2
Bus
LINE
Ground**
Ballast
or
Driver
Switched Hot
Neutral
Dimmed Hot
3-Wire control
3-wire control, C-case, J-case or M-case 3-wire control, K-case
(View from bottom)
** Ballast is grounded via case.
Features
1
Power and terminals accept
only one 16-18 AWG
(0.75 to 1.5 mm
2
) wire
1
E1
E2
NEU
HOT
DH
Class 2
Bus
LINE
Ballast
Ground**
N/C
Dimmed Hot
Neutral
Switched Hot
3-wire control, G-case
1
3-wire control, A-case
Ground**
NEU
HOT
DH
Ballast
Dimmed Hot
Neutral
Switched Hot
Ground
HOT
NEU
DH
Ballast
or
Driver
GND
E1
E2
LINE
Class 2
Bus
Neutral
Switched Hot
Dimmed Hot
1
1
Terminals may be
located on side
and bottom.
K-case can be
grounded via case
or ground terminal.
Appendix |Appendix |
70 | Lutron Lutron | 71
Control wiring diagrams Control wiring diagrams