Control wiring overview
Class 2 must be separated from Class 1 and line
voltage wiring by 0.25 in (6 mm) or a physical barrier
Sensors cannot connect directly to the ballast
or driver
Control wire colors may not match ballast or driver
wire colors
Technical wiring details
Power input terminals only accept one 16-18 AWG
or 0.75 mm
2
-1.5 mm
2
solid copper wire per terminal
Ballasts, drivers and lighting fixtures must be
effectively grounded
Ballasts and drivers must be installed per national
and local electrical codes
E1
E2
NEU
HOT
DH
Class 2
Bus
LINE
Ground**
Ballast
or
Driver
Switched Hot
Neutral
Dimmed Hot
3-Wire control
3-wire control, C-case, J-case or M-case 3-wire control, K-case
(View from bottom)
** Ballast is grounded via case.
Features
1
Power and terminals accept
only one 16-18 AWG
(0.75 to 1.5 mm
2
) wire
1
E1
E2
NEU
HOT
DH
Class 2
Bus
LINE
Ballast
Ground**
N/C
Dimmed Hot
Neutral
Switched Hot
3-wire control, G-case
1
3-wire control, A-case
Ground**
NEU
HOT
DH
Ballast
Dimmed Hot
Neutral
Switched Hot
Ground
HOT
NEU
DH
Ballast
or
Driver
GND
E1
E2
LINE
Class 2
Bus
Neutral
Switched Hot
Dimmed Hot
1
1
Terminals may be
located on side
and bottom.
K-case can be
grounded via case
or ground terminal.