Cut Sheet
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Sensors LOS-CDT Series Occupancy Sensors
369653c 7 02.07.13
Using the Infrared Mask
Center Ceiling Mount
(Mask blocks sensor seeing
out doorway into hall)
Corner Ceiling Mount
(No mask needed)
Conference
Room Mask
180° Mask Full Mask
Rectangular
Areas
Over the Door Specific Areas
You Wish to
Mask
Typical Mask Patterns
Mounting
Normal Mounting
Twist and lock threaded mounting post onto cover
plate. Drill through ceiling tile with assembly, using
cutter end of the threaded mounting post. Secure
with washer and nut.
Cutter
end
Mounting to Non-Standard Ceiling or Fixture
Mount twist-lock cover plate using mounting screws,
nuts, and washers (included). Drill/punch wire routing
hole through ceiling tile at center of cover plate.
Mounting Plate Dimensions
4.2 in
(106.6 mm)
2.5 in
(63 mm)
0.52 in
(13.3 mm)
13/16 in (21 mm)
Wire Lengths
Number of Sensors 1 2 3 1 2 1
Number of Auxiliary
Power Packs
0 0 0 1 1 2
22 AWG 750 ft 375 ft 250 ft 375 ft 250 ft 250 ft
0.5 mm( 365 m 180 m 120 m 90 m 120 m 120 m
20 AWG 1200 ft 600 ft 400 ft 600 ft 400 ft 400 ft
0.75 mm( 730 m 365 m 240 m 365 m 240 m 365 m
18 AWG 2400 ft 1200 ft 800 ft 1200 ft 800 ft 800 ft
7