product specifications
Ganging and Derating
Load Type and Capacity
When combining controls in the same wallbox, derating is required. See Load Type and Capacity.
No derating is required for companion devices.
Control Load Type Not Ganged End of Gang Middle of Gang Neutral
Connection
RRT-G25LW
1,2
LED 250 W 250 W 250 W
Optional
MLV
Halogen
3,4,5
400 VA
(300 W )
400 VA
(300 W )
400 VA
(300 W )
Incandescent /
Halogen
600 W 500 W 400 W
Lutron
Hi-lume
1% 2-wire
LED driver
8
3.3 A (400 W),
10 drivers max
3.3 A (400 W),
10 drivers max
3.3 A (400 W),
10 drivers max
Dimmable
Fluorescent
6
3.3 A (400 VA) 3.3 A (400 VA) 3.3 A (400 VA) Required
RRT-G5NEW
1,2
LED 250 W 250 W 250 W
Required
MLV
Halogen
3,4,5
400 VA
(300 W )
400 VA
(300 W )
400 VA
(300 W )
Incandescent /
Halogen / ELV
4
500 W 400 W 300 W
Lutron
Hi-lume
1% 2-wire
LED driver
8
3.3 A (400 W),
10 drivers max
3.3 A (400 W),
10 drivers max
3.3 A (400 W),
10 drivers max
Dimmable
Fluorescent
6
3.3 A (400 VA) 3.3 A (400 VA) 3.3 A (400 VA)
RRT-G5ANSW
2,7
Lighting 5 A (600 W) 4.1 A (500 W) 3.3 A (400 W)
Required
Fan 3 A (360 W) 3 A (360 W) 3 A (360 W)
Motor 1/10 HP 1/10 HP 1/10 HP
Mixed 3 A (360 W) 3 A (360 W) 3 A (360 W)
1
Designed for use with permanently installed LED, incandescent, tungsten halogen, or magnetic low voltage transformers with halogen based lamps.
2
Power Boosters / Load Interfaces: can be used to control power boosters / load interfaces. For a list of compatible power boosters / load interfaces see Compatible Power Boosters and
Load Interfaces. When using with power boosters/load interfaces, the neutral must be connected.
3
Low-Voltage Applications: Use only with magnetic (core and coil) low-voltage transformers with halogen based lamps. Not recommended for use with electronic (solid-state) low-voltage
transformers but UL listed for dimmable ELV transformers.
4
Operation of a low-voltage circuit with lamps inoperative or removed may result in transformer overheating and premature failure. Lutron strongly recommends the following:
• Do not operate low-voltage circuits without operative lamps in place.
• Replace burned-out lamps as soon as possible.
• Use transformers that incorporate thermal protection or fused transformer primary windings to prevent transformer failure due to overcurrent.
5
When using the dimmer / switch to control MLV halogen fixtures, the maximum lamp wattage is determined by the efficiency of the transformer, with 70%–85% as typical. For actual
transformer efficiency, contact either the fixture or transformer manufacturer. The total VA rating of the transformer(s) shall not exceed the VA rating of the dimmer / switch.
6
Includes Mark X, Tu-Wire, and POWERSENSE.
7
Not for use with receptacles or appliances (e.g., garbage disposals). See Application Note #109 for compatibility with dimmed receptacles.
8
Neutral required for Lutron Hi-lume 1% 2-wire LED driver and fixture.