Cut Sheet

RF Local Controls
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Maestro Wireless® Designer-style: Maestro®
369143m 14 03.04.14
1
When using controls in single-location installations, tighten the blue terminal. Do not connect the blue terminal to any other wiring or to ground.
2
Up to nine Maestro® Companion Switches may be connected to the Maestro Wireless® Switch. Total blue terminal wire length may be up to 250 ft (76 m).
3
Neutral-wire Switches must be connected on the Load side of a multi-location installation.
Wiring Diagrams (continued)
Single-Location Switch Installation with Power Booster Single Feed
MRF2-6ANS, -8ANS-120 with PHPM-SW-DV-WH
Switch
Brass Blue
1
Zone In
Black
Silver
Hot/Live
Switched Hot
Hot/Live
NeutralNeutral
Neutral
Ground
Ground
Green
120 V~ 60 Hz
Load
Multi-Location Switch Installation with Power Booster Single Feed
2,3
MRF2-6ANS, -8ANS-120 with MA-AS / MSC-AS and PHPM-SW-DV-WH
Companion Switch Switch
Brass BlueBlue
Zone In
Black
Silver
Hot/Live
Switched Hot
Hot/Live
Brass
Black
NeutralNeutral
Neutral
Ground
Ground
Green
Ground
Green
120 V~ 60 Hz
Load