Cut Sheet

RF Local Controls
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Maestro Wireless® Designer-style: Maestro®
369143m 7 03.04.14
Specifications
Regulatory Approvals
UL Listed.
cUL Listed (MRF2-6CL only).
CSA Certified (except for MRF2-6CL).
FCC Approved. Complies with the limits for a Class B
digital device, pursuant to Part 15 of the FCC Rules.
Industry Canada Certified.
Power
Operating voltage:
120 V~ 50/60 Hz (all models)
277 V~ 50/60 Hz (MRF2-8S-DV, MRF2-F6AN-DV)
Key Design Features
Dimmers
On a single-tap, lights fade UP or DOWN.
On a double-tap, lights go to full ON.
When ON, press and hold to engage 20-second fade
to OFF.
Light levels can be fine-tuned by pressing and
holding the dimming rocker until the desired light
level is reached.
Two-wire dimmers available.
Switches
On a single-tap, lights turn ON or OFF.
Two-wire switches available.
All RF Local Controls
Tested to withstand electrostatic discharge without
damage or memory loss, in accordance with IEC
61000-4-2.
Tested to withstand surge voltages without damage
or loss of operation, in accordance with IEEE
C62.41-1991 Recommended Practice on Surge
Voltages in Low-Voltage AC Power Circuits.
Controls always operate locally and do not require
system control.
Power failure memory: should power be interrupted,
the control will return to its previously-set level prior
to the interruption when power is restored.
Uses conventional 3-way and 4-way wiring.
Multiple location control from Dimmer/Switch and up
to nine Companion Dimmers/Switches.
Use Lutron® Designer (Claro® and Satin Colors®)
wallplates or designer-style wallplates from other
manufacturers. Wallplates are sold separately.
Lutron Claro® and Satin Colors® wallplates snap on
with no visible means of attachment.
Requires a one-gang U.S. wallbox; 3
1
2 in (89mm)
deep recommended, 2
1
4 in (57 mm) deep minimum.
Green indicator lights.
System Communications and Capacity
Maestro Wireless® controls communicate with the
Pico® wireless controls and Radio Power SavrTM
sensors through radio frequency (RF).
Maestro Wireless® local controls must be located
within 60 ft (18 m) line-of-sight or 30 ft (9 m) through
walls, of Radio Power SavrTM sensors.
Maestro Wireless® local controls must be located
within 100 ft (30 m) line-of-sight or 30 ft (9 m)
through walls, of a Pico® wireless control.
Up to ten Maestro Wireless® controls can be
configured to work together.
Environment
Ambient operating temperature: 32 °F to 104 °F
(0°C to 40 °C), 0%–90% humidity, non-condensing.
Indoor use only.