Information Sheet

®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Caséta Wireless Load Controls
369987g 4 06.28.19
Load Type and Capacity - Switches and Fan Control
Model Number Description Voltage Load Type
Minimum
Load
Maximum Load
3
Not Ganged End of Gang Middle of Gang
PD-5WS-DV
1
Two-wire
switch
120 V~
Incandescent /
Halogen
25 W 600 W 450 W 350 W
277 V~
Incandescent /
Halogen
25 W 1350 W 110 0 W 800 W
120 V~ MLV 25 W 600 VA / 475 W 450 VA / 350 W 350 VA / 275 W
277 V~ MLV 25 W 1350 VA / 1075 W 1100 VA / 875 W 800 VA / 625 W
120 V~
General
Purpose Fan
0.4 A 3 A 3 A 3 A
120 / 277 V~ LED Use LUT-MLC
2
5 A 4 A 3 A
120 / 277 V~ Fluorescent Use LUT-MLC
2
5 A 4 A 3 A
120 V~ ELV Use LUT-MLC
2
600 W 450 W 350 W
277 V~ ELV Use LUT-MLC
2
1350 W 110 0 W 800 W
PD-5ANS
Neutral-wire
switch
(neutral
connection
required)
120 V~
Incandescent /
Halogen
10 W 600 W 600 W 600 W
MLV 10 W 600 VA 600 VA 600 VA
Fan 0.1 A 3 A 3 A 3 A
LED 1 bulb 5 A 5 A 5 A
Fluorescent 1 ballast 5 A 5 A 5 A
ELV 10 W 600 W 600 W 600 W
PHPM-SW 1 interface 2 interfaces 2 interfaces 2 interfaces
PD-6ANS
Neutral-wire
switch
(neutral
connection
required)
120 V~
Incandescent /
Halogen
10 W 720 W 720 W 600 W
MLV 10 W 720 VA 720 VA 600 VA
Fan 0.1 A 3.6 A 3.6 A 3.6 A
LED 1 bulb 6 A 6 A 5 A
Fluorescent 1 ballast 6 A 6 A 5 A
ELV 10 W 720 W 720 W 600 W
PHPM-SW 1 interface 3 interfaces 3 interfaces 3 interfaces
PD-FSQN
4
Fan speed
control
(neutral
connection
required)
120 V~
Single Ceiling
Fan
(Permanent
split-capacitor
motor)
0.1 A 1.5 A 1.5 A 1.5 A
1
No neutral wire required.
2
To ensure proper operation of the switch with LED, fluorescent, and ELV loads, a LUT-MLC (included) may be required, especially at lower wattages. If the
status LED on the switch is flashing or solid red in color, a LUT-MLC must be installed. To guarantee best performance, installing a LUT-MLC with these load
types regardless of wattage is recommended. Rarely, some load types may still flicker or glow in the off state even with the LUT-MLC installed, in which case
a different load may be required or more than one LUT-MLC is required.
3
See “Ganging and Derating” section.
4
Not for use with fans that have integrated fan speed and / or light control modules, DC motor fans, fans with remote controls, bathroom or kitchen exhaust
type fans.