Installation Manual

Phase Select Dimming Module Installation
Vive PowPak Phase Select Dimming module
Vive Emergency PowPak Phase Select Dimming module
Test
Link
Cal.
PowPak module Wireless Transmitters
At least one phase dimmable lighting load (incandescent, halogen, LED, fluorescent, ELV, or MLV)
System Components
Radio Powr Savr
Occupancy / Vacancy Sensor
(10 maximum per PowPak module)
Radio Powr Savr
Daylight Sensor
(1 maximum per PowPak module)
Pico Remote Control
(10 maximum per
PowPak module)
Note: All drivers and ballasts used with Vive wireless controls must comply with the
limits pursuant to CAN ICES-005 and the FCC rules.
lutron.com
RMJS-PNE-DV
120 / 277 V~ 50 / 60 Hz
50019498a
Raise
Toggle
Lower
Indicator LED
Consult third-party fixtures installation guide for fixture-specific wiring.
Occupancy Sensors
Daylight Sensor
Wireless Controls
Occupied: All lights 100%.
Unoccupied: All lights off.
Test
Link
Cal.
All lights dim in response to daylight.
On All lights 100%
Favorite All lights 50%
Off All lights off
Default Functionality
2
A
PowPak module must be installed in a metal 101.6 mm x
101.6 mm (4 in x 4 in) junction box (minimum depth 54 mm (2.125
in) with mounting screws (provided). Please consult local and
national electric codes for proper installation. Note: if PowPak
module cannot be fully seated into the junction box, try rotating
the PowPak module 90, 180, or 270 degrees. Or move conduit
hardware to a different knockout hole. If neither option works, an
extension ring may be required.
English
All Wireless Transmitters
must be installed within
30 ft (9 m) of the
PowPak module.
450 W Incandescent / Halogen
450 VA LED (reverse-phase)
3 A Lutron Hi-lume 1% 2-wire LED driver (13 drivers max)
200 W LED NEMA SSL 7A-2015
450 W ELV
400 VA MLV
400 VA Fluorescent
0 W minimum load
120 / 277 V~ 50 / 60 Hz
RMJS-PNE-DV
RMJS-PNE-DV-EM
lutron.com
RMJS-PNE-DV
120 / 277V~ 50 / 60 Hz
50019498a
Radio Powr Savr
Occupancy
Sensor
Pico
Remote
Control
PowPak
module
30 ft
(9 m) max
40 ft (12 m)
33 ft (10 m)
Phase Select PowPak
Install in center of room to
maximize RF coverage.
1
WARNING! Shock Hazard. May result in serious injury or death. Turn off power at circuit
breaker before installing the unit.
lutron.com
RMJS-PNE-DV
120 / 277 V~ 50 / 60 Hz
50019498a
Dimmed Line / Hot (Red)
Line / Hot (Black)
To Fixtures
Neutral (White)
Neutral
Junction Box
Important Notes: Please read before installing.
For installation by a qualified electrician in accordance with all local and national electrical codes.
Note: Use copper conductors only.
Check to see that the device type and rating is suitable for the application.
DO NOT install if product has any visible damage.
If moisture or condensation is evident, allow the product to dry completely before installation.
Operate between 0 °C and 40 °C (32 °F and 104 °F) ambient.
0% to 90% humidity, non-condensing.
For indoor use only.
For spec submittal, see http://www.lutron.com/TechnicalDocumentLibrary/3691150.pdf
For application note, see http://www.lutron.com/TechnicalDocumentLibrary/048781.pdf
Operation of a low-voltage circuit with removed or inoperative lamps may result in transformer overheating
and premature failure. Lutron strongly recommends the following:
a. Do not operate low-voltage circuits without operative lamps in place.
b. Replace burned-out lamps as quickly as possible.
c. Use transformers that incorporate thermal protection or fused transformer primary windings to prevent
transformer failure due to overcurrent.
Lutron Electronics Co., Inc. 7200 Suter Road
Coopersburg, PA 18036-1299 USA
Start Here
Mount, Wire, and Install Phase Dimmable
Devices and Lighting Fixtures
Consult third-party device installation guide
Locate PowPak module
Suggested Installation Location: Center of room
to ensure proper RF coverage of area. For optimal
RF performance: PowPak module must not be fully
enclosed in metal. No metal should exist anywhere
within 200 mm (8 in) in front of the front plate of the
PowPak module. Mount a minimum of 0.6 m (2 ft)
away from the controlled fixture. Ensure the junction
box is well grounded (preferably via a metal conduit
between the controlled fixture and the PowPak module
junction box).
Customer Assistance www.lutron.com/support
Troubleshooting www.lutron.com/support
041769
Rev. A
01/2021
Part of the Vive Family
Wire Connector Information
(1-3) 4.0 mm
2
(10 AWG)
(1-3) 2.5 mm
2
(12 AWG)
(1-3) 1.5 mm
2
(14 AWG)
(1-2) 4.0 mm
2
& (1) 2.5 mm
2
(10 & 12 AWG)
(1-2) 4.0 mm
2
& (1) 1.5 mm
2
(10 & 14 AWG)
(1-2) 2.5 mm
2
& (1) 1.5 mm
2
(12 & 14 AWG)
(1-2) 4.0 mm
2
& (1) 1.0 mm
2
(10 & 16 AWG)
(1-2) 2.5 mm
2
& (1) 1.0 mm
2
(12 & 16 AWG)
(1-2) 1.5 mm
2
& (1) 1.0 mm
2
(14 & 16 AWG)
(1-2) 4.0 mm
2
& (1) 0.75 mm
2
(10 & 18 AWG)
(1-2) 2.5 mm
2
& (1) 0.75 mm
2
(12 & 18 AWG)
(1-2) 1.5 mm
2
& (1) 0.75 mm
2
(14 & 18 AWG)
Red
Yellow
1/2 in (13 mm):
10, 12, & 14 AWG
(4.0, 2.5, &
1.5 mm
2
)
5/8 in (16 mm):
16 & 18 AWG
(1.0 & 0.75 mm
2
)
(1-3) 10 AWG (4.0 mm
2
)
(1-3) 12 AWG (2.5 mm
2
)
(1-3) 14 AWG (1.5 mm
2
)
(1-2) 10 AWG & (1) 12 AWG (4.0 & 2.5 mm
2
)
(1-2) 10 AWG & (1) 14 AWG (4.0 & 1.5 mm
2
)
(1-2) 12 AWG & (1) 14 AWG (2.5 & 1.5 mm
2
)
(1-2) 10 AWG & (1) 16 AWG (4.0 & 1.0 mm
2
)
(1-2) 12 AWG & (1) 16 AWG (2.5 & 1.0 mm
2
)
(1-2) 14 AWG & (1) 16 AWG (1.5 & 1.0 mm
2
)
(1-2) 10 AWG & (1) 18 AWG (4.0 & 0.75 mm
2
)
(1-2) 12 AWG & (1) 18 AWG (2.5 & 0.75 mm
2
)
(1-2) 14 AWG & (1) 18 AWG (1.5 & 0.75 mm
2
)
3/8 in (10 mm):
12 & 14 AWG
(2.5 & 1.5 mm
2
)
7/16 in (11 mm):
16 & 18 AWG
(1.0 & 0.75 mm
2
)
(1-3) 12 AWG (2.5 mm
2
)
(2-3) 14 AWG (1.5 mm
2
)
(1-2) 12 AWG & (1) 14 AWG (2.5 & 1.5 mm
2
)
(1-2) 12 AWG & (1) 16 AWG (2.5 & 1.0 mm
2
)
(1-2) 14 AWG & (1) 16 AWG (1.5 & 1.0 mm
2
)
(1-2) 12 AWG & (1) 18 AWG (2.5 & 0.75 mm
2
)
(1-2) 14 AWG & (1) 18 AWG (1.5 & 0.75 mm
2
)
13 mm (1/2 in):
4.0, 2.5, & 1.5 mm
2
(10, 12, & 14 AWG)
16 mm (5/8 in):
1.0 & 0.75 mm
2
(16 & 18 AWG)
Red
lutron.com
RMJS-PNE-DV
120 / 277 V~ 50 / 60 Hz
50019498a
1.25
(31.8)
2.82
(71.6)
3.94
(100.1)
200 mm
(8 in)
200 mm
(8 in)
200 mm
(8 in)
200 mm
(8 in)
200 mm
(8 in)
Keep metal
at least
200 mm
(8 in) away
200 mm
(8 in))
200 mm
(8 in)
Note: RMJS-PNE-DV-EM requires the use of an automatic transfer switch to change from normal to emergency power. Refer to
048628 for wiring diagrams on www.lutron.com
If installing an emergency PowPak module and the wiring needs to be verified, follow “Reset Factory Defaults” procedure to exit
emergency mode.
Please note that any programming will be lost and will have to be reprogrammed. Only perform this step during initial installation
and wiring verification.
Note: For periodic testing and maintanance of emergency systems, use a toggle switch or breaker to ensure proper operation.
Refer to App Note # 781 (P/N 048781) on www.lutron.com for procedure.
Note: Momentary power outages can envoke emergency mode on the PowPak module. SeeTroubleshooting section for details.
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be
followed including the following:
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS
Do not use outdoors.
Do not mount near gas or electric heaters.
Equipment should be mounted in locations and at heights where it will not be
subjected to tampering by unauthorized personnel.
The use of accessory equipment not recommended by the manufacturer may
cause an unsafe condition.
Do not use this equipment for other than its intended use.
SAVE THESE INSTRUCTIONS
Phase Selection
4
Most loads are expected to use the default setting of reverse-phase, however some require forward-phase for proper functionality.
A
Connect bare copper wire from junction box to green ground screw, and
power wires to appropriate power and load connections.
B
Once installed, energize the PowPak module.
C
Use the Toggle button “ u to toggle between high-end and OFF to
verify ballasts or LED drivers wiring.
D
Use the Raise
and Lower
Δ
” buttons to verify control wiring.
3
Install PowPak module
NOTE: Output must NOT be used to control receptacles. Output must be directly connected to the load.
Output breakers or switches must not be used.
Ground (Green screw)
See page 2 for Programming
Vive Hub
A Enter Phase Selection mode.
Press and hold Raise ” & Lower ” buttons for 12 seconds. Indicator LED will flash and load will fade to OFF.
B Pressing the
Raise button “ ” sets the current phase to forward-phase, and pressing the Lower button “ ” sets the current phase to reverse-phase.
Indicator LED Feedback:
(Reverse-phase): Flashes 1 time with a 1 second interval and then turns OFF for 2 seconds
(Forward-phase): Flashes 2 times with a 1 second interval and then turns OFF for 1 second
C
Press and hold the Toggle button for 6 seconds. Indicator LED will flash for 5 seconds. Load will fade to full ON.
Reset Factory Defaults
Note: In some instances, it may be necessary to reset the PowPak module and
connected devices back to factory default settings. Before beginning, make sure that
all devices are connected and powered.
A
Triple-tap the Toggle button “ uon the PowPak module and hold until the LED begins
to flash slowly; release button.
B
Within 3 seconds of the start of flashing, triple-tap the same button again and the
LEDs will flash rapidly indicating that the unit has been reset to factory defaults.
Note: Any associations or programming previously set up with the PowPak module
will be erased and will need to be re-programmed.
Issue
Solution
Fixtures cannot be controlled locally from PowPak module.
Ensure that the breaker(s) to the PowPak module are energized.
Ensure that the PowPak module dimmed hot lead is wired to the lighting fixture(s).
PowPak module may be in emergency mode.
Reset PowPak module to factory defaults. See www.lutron.com/vivevideos
Lights do not dim as expected.
Ensure that dimmed hot lead is wired properly.
PowPak module may be in emergency mode.
Lights do not respond to Wireless Transmitter(s) (Pico remotes and RPS sensors).
Ensure that the breaker(s) to the PowPak module and any connected ballasts or LED drivers are energized.
Ensure that Wireless Transmitters are associated to the PowPak module.
Reset PowPak module to factory defaults. See www.lutron.com/vivevideos
Lights are unstable at low-end (or high-end) or flash / flicker at turn-on or turn-off. Adjust low-end (or high-end) trim.
Wireless Transmitter(s) (Pico remotes or RPS sensors) cannot be associated to PowPak module. The maximum number of Wireless Transmitters have been associated to the PowPak module. To remove a previously set up Wireless Transmitter. See www.lutron.com/vivevideos
Load Type Phase
Incandescent / Halogen Reverse
LED
NEMA SSL 7A-2015 Forward
Lutron Hi-lume 1% 2-wire LED driver Forward
Other LED drivers and self-ballasted lamps Reverse
ELV Reverse
MLV Forward
Fluorescent Forward