Cut Sheet

product specifications
09.25.15369968a
RadioRA® 2 C
L® Hybrid Keypads
5 Technical Support: 1.800.523.9466 (U.S.A)www.lutron.com
Load Type and Capacity
A
Not Ganged
B
End of Gang
C
Middle of Gang
Load Type
1
Minimum Load Maximum Load
Incandescent/Halogen 15 W 450 W 350 W 250 W
CFL/LED See compatible list
4
100 W 100 W 100 W
MLV
2
15 W/VA 350 W/450 VA 250 W/350 VA 200 W/250 VA
Hi-lume® A-Series LTE LED Driver
3
1 driver 150 W 100 W 100 W
1
Load Type: C
L® Hybrid Keypads are designed for use with permanently installed incandescent, tungsten halogen, CFL/LED, magnetic
low-voltage, or Lutron® Hi-lume® A-Series LTE LED drivers only. To reduce the risk of overheating and possible damage to other
equipment, do not install C
L® Hybrid Keypads to control receptacles, ELV loads, or motor-operated appliances.
2
Low-Voltage Applications: Use C
L® Hybrid Keypads with magnetic (core and coil) low-voltage transformers only. Not for use with
electronic (solid-state) low-voltage transformers. Operation of a low-voltage circuit with lamps inoperative or removed may result in
transformer overheating and premature failure. Lutron strongly recommends the following:
Do not operate low-voltage circuits without operative lamps in place.
Replace burned-out lamps as quickly as possible.
Use transformers that incorporate thermal protection or fused transformer primary windings to prevent transformer failure due to
overcurrent.
3
Each C
L® Hybrid Keypad may have a maximum of 10 Lutron® 150 W Hi-lume® A-series LTE LED drivers.
4
For a complete list of compatible Dimmable CFLs and LEDs, please visit www.lutron.com/ledtool
Mixed-Load Derating Chart
Total CFL/LED Wattage
Total Incandescent/Halogen Wattage
A: Not Ganged B: End of Gang C: Middle of Gang
0 W + 15 W – 450 W Or 15 W – 350 W Or 10 W – 250 W
1 W – 25 W + 0 W – 350 W Or 0 W – 250 W Or 0 W – 100 W
26 W – 50 W + 0 W – 250 W Or 0 W – 150 W Or 0 W – 50 W
51 W – 75 W + 0 W – 150 W Or 0 W – 50 W Or 0 W
76 W 100 W + 0 W Or 0 W Or 0 W
Compatible Power Boosters and Load Interfaces
Some local controls can be used to control power boosters or load interfaces. Up to three power
boosters or load interfaces can be used with one control. See table below for a list of compatible
power boosters and load interfaces.
Control Phase Adaptive
Power Modules:
PHPM-PA-120-WH,
PHPM-PA-DV-WH
3-wire Fluorescent
Power Modules:
PHPM-3F-120-WH,
PHPM-3F-DV-WH
Switched Power
Module:
PHPM-SW-DV-WH
0 –10 V Interface and
Switching Module:
GRX-TVI
RRD-HN1RLD
P P P P
RRD-HN2RLD
RRD-HN3BSRL
RRD-HN3S
RRD-HN4S
RRD-HN5BRL
RRD-HN6BRL
A B B B C B