Installation Manual
97
Lutron integration protocol
Palladiom Keypad (continued)
DEVICE Commands (continued)
DEVICE Command-specific fields (continued)
Action Numbers and Parameters:
Action Action Number Parameters
Set (#) Press 3 None
Set (#) Release 4 None
Set (#) Hold 5 None
Set (#) Multi-tap 6 None
Set (#) or Get (?) LED State
1
9 0 = Off
1 = On
2 = Normal-Flash: 1 flash every second
1
3 = Rapid-Flash: 10 flashes every second
1
Set (#) or Get (?) Active LED
Level
1,2
36 0 –100
Set (#) or Get (?) Inactive LED
Level
1,2
37 0 –100
NOTES
1. “Set” is for unprogrammed buttons and buttons with LED logic ‘Defined by Integration.’
2. LED intensity can be set only when the DBM sensor is disabled.
Example DEVICE Commands
Examples presume keypad has been assigned Integration ID 2.
Operation Command String
Execute: #DEVICE, Integration ID, Component Number, Action Number, Parameters
Set Active LED to 50 #DEVICE,2,89,36,50<CR><LF>
Query: ?DEVICE, Integration ID, Component Number, Action Number
What is the Inactive LED Level? ?DEVICE,2,113,37<CR><LF>
Response: ~DEVICE, Integration ID, Component Number, Action Number, Parameters
Inactive LED Level is 75% ~DEVICE,2,113,37,75<CR><LF>
Scene 1
Scene 2
Scene 3