OUTPUT Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Set (#) or Get (?) Zone Level 1 0–100 or
0.00–100.00
SS.ss
1
, SS, MM:SS, or HH:MM:SS
Set (#) Start Raising 2 None
Set (#) Start Lowering 3 None
Set (#) Stop Raising or Lowering 4 None
Set (#) Start Flashing
2
5 SS.ss
1
, SS, MM:SS, or HH:MM:SS
Set (#) Pulse Time 6
SS.ss
1
, SS, MM:SS, or HH:MM:SS
Set (#) or Get (?) tilt level
3,4
9 Tilt Level
5
= 0 –100
6
or 0.00–100.00
5,6
Fade
1
in: SS.ss
2
, SS, MM:SS, or HH:MM:SS
Delay
3
in: SS.ss
2
, SS, MM:SS, or HH:MM:SS
Set (#) or Get (?) lift & tilt level
4
10 Lift Level
5
= 0 –100 or 0.00 –100.00
5
Tilt Level
5
= 0 –100
f
or 0.00–100.00
5,6
Fade
1
in: SS.ss
2
, SS, MM:SS, or HH:MM:SS
Delay
3
in: SS.ss
2
, SS, MM:SS, or HH:MM:SS
Set (#)
Start Raising Tilt
4
11 None
Set (#)
Start Lowering Tilt
4
12 None
Set (#)
Stop Raising or Lowering Tilt
4
13 None
Set (#)
Start Raising Lift
4
14 None
Set (#)
Start Lowering Lift
4
15 None
Set (#)
Stop Raising or Lowering Lift
4
16 None
Set (#) DMX Color or Level Settings
7, 8
17 Color / level index: 0– 255 / 0.00–100.00
Set (#) Motor Jog Raise
7, 9
18 None
Set (#) Motor Jog Lower
7, 9
19 None
Set (#) Motor 4-Stage Jog Raise
7, 9
20 None
Set (#) Motor 4-Stage Jog Lower
7, 9
21 None
NOTES
1. Fractions are rounded up to the closest 1/4 second.
2. To stop a dimmer from flashing, send it to a valid level (action 1).
3. The Delay time is optional. When not used, the system will use a zero-second delay. The minimum delay time is
0seconds. The maximum delay time is 4 hours.
4. Not supported in Quantum.
5. For switched outputs, any non-zero level results in on or closed, 0 results in off or open.
6. 50 for Horizontal Sheer Blinds.
7. Not supported in RadioRA 2.
8. Supported in Quantum version 2.2 and higher.
9. Supported in Quantum version 2.5 and higher.
Lutron integration protocol
OUTPUT Command Format
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#OUTPUT, 6, Action Number, Parameters
Integrator’s Reference (continued)
OUTPUT: Command Summary
Outputs are dimmers, CCOs, or other devices in a system that have a controllable output. All of
these devices will accept levels from 0% to 100% and 0.00% to 100.00% with a given fade and
delay time. These same commands can be monitored as they occur in the system.