Installation Manual

120
Lutron integration protocol
Dynamic Keypad (continued)
DEVICE Commands
DEVICE Command Formats
DEVICE Command-specific fields
Component Numbers:
Component Component Number Available Actions
Button 1 (left hard button) 1 Press, Release
Button 2 (middle hard button) 2 Press, Release
Button 3 (right hard button) 3 Press, Release
Button N
1
N Press, Release
LED M
1
M Set or Get LED state
NOTE
1. Component Numbers for the various pages of buttons and LEDs for a Dynamic Keypad are generated by the
HomeWorks QS or myRoom Software.
Action Numbers and Parameters:
Action Action Number Parameters
Set (#) Press 3 None
Set (#) Release 4 None
Set (#) Hold 5 None
Set (#) Multi-tap 6 None
Set (#) or Get (?) LED State 9
0 = Off
1 = On
2 = Normal-Flash
3 = Rapid-Flash
Example DEVICE Commands
Examples presume the Dynamic Keypad has been assigned Integration ID 23.
Operation Command String
Execute: #DEVICE, Integration ID, Component Number, Action Number, Parameters
Press Button 118. #DEVICE,23,118,3<CR><LF>
Turn On LED 566. #DEVICE,23,566,9,1<CR><LF>
Query: ?DEVICE, Integration ID, Component Number, Action Number
What is the state of LED 566? ?DEVICE,23,566,9<CR><LF>
Response: ~DEVICE, Integration ID, Component Number, Action Number, Parameters
LED 1 is On. ~DEVICE,23,566,9,1<CR><LF>
Use “DEVICE Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#DEVICE, 2, Component Number, Action Number, Parameters