Installation Manual

128
Lutron integration protocol
Sivoia QS Venetian Blind (continued)
OUTPUT Commands
OUTPUT Command Format
OUTPUT Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Set (#) or Get (?) Lift Level 1
Lift Level
1
= 0 –100 or 0.00 –100.00
Fade
2
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Delay
4
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Set (#) or Get (?) Tilt Level 9
Tilt Level
1
= 0 –100 or 0.00 –100.00
Fade
2
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Delay
4
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Set (#) or Get (?) Lift and Tilt Levels 10
Lift Level
1
= 0 –100 or 0.00 –100.00
Tilt Level
1
= 0 –100 or 0.00 –100.00
Fade
2
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Delay
4
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Set (#) Start Raising Tilt 11 None
Set (#) Start Lowering Tilt 12 None
Set (#) Stop Raising or Lowering Tilt 13 None
Set (#) Start Raising Lift 14 None
Set (#) Start Lowering Lift 15 None
Set (#) Stop Raising or Lowering
Lift
16 None
NOTES
1.
2.
Fade is not available for blinds since they move at a constant rate. The parameter must be entered but is ignored.
3. Fractional seconds “SS.ss” will be rounded down to the nearest quarter second. For example, if a delay time is specified
as 1.45 seconds, a value of 1.25 seconds will be used.
4. The Delay time is optional. When not used, the system will use a zero-second delay. The minimum delay time is
0.25seconds. The maximum delay time is 4 hours. Not supported in QS Standalone.
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#OUTPUT, 1, Action Number, Parameters
100% 75% 50% 25% 0%
Lift
Tilt