Installation Manual

10
Lutron integration protocol
Integrator’s Reference (continued)
HVAC: Command Summary
HVAC Integration commands allow the user to access the HVAC components and features of the
system. The user can modify HVAC parameters like the operating mode, fan mode etc., as well as
monitor the changes to these parameters as they occur in the system.
HVAC Command Format
Use “HVAC Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#HVAC,21, Action Number, Parameters
HVAC Command-specific fields
Action Numbers and Parameters:
1
Action Action Number Parameters
Set (#) or Get (?) Current Temperature (°F)
5
1 Temperature = 32–212 °F
Set (#) or Get (?) Heat and Cool
Setpoints (°F)
2, 4, 5
2
Setpoint Heat (SPH) = 32–212 °F
Setpoint Cool (SPC) = 32–212 °F
Set (#) or Get (?) Operating Mode 3
Mode (1 = Off/Protect, 2 = Heat, 3 = Cool, 4 = Auto,
5 = Em.Heat, 7= Fan, 8 = Dry)
Set (#) or Get (?) Fan Mode 4
Mode (1 = Auto, 2 = On, 3 = Cycler, 4 = No Fan,
5 = High, 6 = Medium, 7 = Low, 8 = Top)
Set (#) or Get (?) Eco (Setback) Mode 5 Mode (1 = Off, 2 = On)
Get (?) Eco Offset 6 Eco Offset = 1–11 °F
Set (#) or Get (?) Schedule Status
3
7
0 = Schedule Unavailable (Get “?” Only)
1 = Following Schedule (Set “#” or Get “?”)
2 = Permanent Hold (Set “#” or Get “?”)
3 = Temporary Hold (Get “?” only)
Get (?) Temperature Sensor
Connection Status
8
1 = All Sensors are Active
2 = Missing Sensor
3 = Wired Sensor Only
4 = No Sensor
Get (?) Schedule Event 9 Schedule # (1–7), Event # (1–4), HH,MM, SPH, SPC
Get (?) Schedule Day Assignment 10
Schedule#(1–7), DD(Bitmap:Sunday(Bit 0)
Saturday(Bit 6) 1–active day, 0 inactive day)
Get (?) System Mode 11
1 = Normal
2 = Away
3 = Green
Get (?) Heat and Cool Setpoints (°F) without
Eco Offset if applied
5
12
Setpoint Heat (SPH) = 32 – 212 °F
Setpoint Cool (SPC) = 32 – 212 °F
Get (?) Emergency Heat Available 13
1 = Not Available
2 = Available
NOTES
1. These commands are supported only for HomeWorks QS, RadioRA 2, myRoom Plus.
2. Changing the setpoint will turn Eco Mode off if it is currently on.
3. Schedule Unavailable –> Schedule not programmed or device needs date / time.
Following Schedule –> Running programmed schedule; set points from schedule.
Permanent Hold –> Schedule is not running; set points as adjusted.
Temporary Hold –> Running schedule; set points as adjusted. Returns to following schedule at next schedule event.
4. To leave a parameter unchanged, use “255” as the value for that parameter when ending the command.
5. Allow for reported temperature values to be zero padded, with up to 3 digits before the decimal point, and 2 digits after.
Possible reported values of 5 °C: “005”, “05”, “5”, “005.”, “005.”, “5.”, “005.0”, “05.0”, “5.0”, “005.00”, “05.00”, “5.00”
Possible reported values of 5.5 °C: “005.5”, “05.5”, “5.5”, “005.50”, “05.50”, “5.50”
Possible reported values of 21 °C: “021”, “21”, “021.0”, “21.0, “021.00,” “21.00”
Possible reported values of 21.5 °C: “021.5”, “21.5”, “021.50”, “21.50”