Installation Manual

144
Lutron integration protocol
Temperature Controls (continued)
HVAC Commands (continued)
Example HVAC Commands
Operation Command String
Execute: #HVAC, Integration ID, Action Number, Parameters
Set heat setpoint to 68 °F and cool setpoint to 72 °F. #HVAC,1,2,68,72<CR><LF>
Set system mode to cool. #HVAC,1,3,3<CR><LF>
Turn Eco mode on. #HVAC,1,5,2<CR><LF>
Set heat setpoint to 18.5 C and cool setpoint to 21.5 C #HVAC,21,16,18.5,21.5<CR><LF>
Query: ?HVAC, Integration ID, Action Number
What is the current temperature? ?HVAC,1,1<CR><LF>
What is are the settings for Schedule 1, Event 2? ?HVAC,1,9,1,2<CR><LF>
What days are running Schedule 1? ?HVAC,1,10,1<CR><LF>
What are the current heat and cool setpoints in Celsius? ?HVAC,21,16<CR><LF>
What are the current heat and cool setpoints in Fahrenheit if the
Celsius values are 18.5 °C and 21.5 °C respectively?
?HVAC,21,2<CR><LF>
What are the current heat and cool setpoints in Fahrenheit if the
Celsius values are 10 °C and 20 °C respectively?
?HVAC,21,2<CR><LF>
Response: ~HVAC, Integration ID, Action Number, Parameters
Current Temperature is 70 °F. ~HVAC,1,1,70<CR><LF>
Schedule 1, Event 2 starts at 8:00 am with SPH=65,SPC=78 ~HVAC,1,9,1,2,08,00,65,78<CR><LF>
Schedule 1 is being run on Monday and Tuesday. ~HVAC,1,10,1,06<CR><LF>
Current heat and cool setpoints in Celsius are 18.5 °C and 21.5 °C
respectively.
~HVAC,21,16,18.5,21.5<CR><LF>
Current heat and cool setpoints in Fahrenheit are 65.3 °F and 70.7 °F
respectively.
~HVAC,21,2,65.3,70.7<CR><LF>
Current heat and cool setpoints in Fahrenheit are 50 °F and 68 °F
respectively.
~HVAC,21,2,50,68<CR><LF>
NOTES
If the thermostat is setup to use Fahrenheit, it is recommended to use Fahrenheit Integration command set. If it is setup
to use Celsius, it is recommended to use the Celsius Integration command set.
• Allow for reported temperature values to be zero padded, with up to 3 digits before the decimal point, and 2 digits after.
Possible reported values of 5 °C: “005”, “05”, “5”, “005.”, “005.”, “5.”, “005.0”, “05.0”, “5.0”, “005.00”, “05.00”, “5.00”
Possible reported values of 5.5 °C: “005.5”, “05.5”, “5.5”, “005.50”, “05.50”, “5.50”
Possible reported values of 21 °C: “021”, “21”, “021.0”, “21.0, “021.00,” “21.00”
Possible reported values of 21.5 °C: “021.5”, “21.5”, “021.50”, “21.50”