Lutron integration protocol
Integrator’s Reference (continued)
HVAC: Command Summary (continued)
HVAC Command-specific fields (continued)
Action Numbers and Parameters (continued):
Action Action Number Parameters
Set (#) or Get (?) Call Status 14
0 = None, Last was Heat
1 = Heat Stage 1
2 = Heat Stage 1 and 2
3 = Heat Stage 1, 2, and 3
4 = Heat Stage 3
5 = None, Last was Cool
6 = Cool Stage 1
7 = Cool Stage 1 and 2
8 = Off
9 = Emergency Heat
10 = Dry
Set (#) or Get (?) Current Temperature (°C)
1, 4
15 Temperature = 0 –100 °C
Set (#) or Get (?) Heat and Cool Setpoints
(°C)
2, 3, 4
16
Setpoint Heat (SPH) = 0 – 100 °C
Setpoint Cool (SPC) = 0 – 100 °C
Get (?) Heat and Cool Setpoints (°C) without
Eco Offset if applied
2, 4
17
Setpoint Heat (SPH) = 0 – 100 °C
Setpoint Cool (SPC) = 0 – 100 °C
Set (#) or Get (?) Single Setpoint (°F) and
Drifts
3, 4
18
Single Setpoint =
32 – 212 °F
Negative Drift =
0 – 15 °F
Positive Drift =
0 – 15 °F
Set (#) or Get (?) Single Setpoint (°C) and
Drifts
3, 4
19
Single Setpoint =
0 – 100 °C
Negative Drift =
0 – 8 °C
Positive Drift =
0 – 8 °C
NOTES
1. HomeWorks QS software version 4.1 and higher.
2. Changing the setpoint will turn Eco Mode off if it is currently on.
3. To leave a parameter unchanged, use “255” as the value for that parameter when ending the command.
4. Allow for reported temperature values to be zero padded, with up to 3 digits before the decimal point, and 2 digits after.
Possible reported values of 5 °C: “005”, “05”, “5”, “005.”, “005.”, “5.”, “005.0”, “05.0”, “5.0”, “005.00”, “05.00”, “5.00”
Possible reported values of 5.5 °C: “005.5”, “05.5”, “5.5”, “005.50”, “05.50”, “5.50”
Possible reported values of 21 °C: “021”, “21”, “021.0”, “21.0, “021.00,” “21.00”
Possible reported values of 21.5 °C: “021.5”, “21.5”, “021.50”, “21.50”