Installation Manual

23
Lutron integration protocol
QS Standalone (continued)
System Commands (continued)
PROGRAMMING Commands
PROGRAMMING Command-specific fields
Action Numbers and Parameters:
Description Action Number Parameters
Set (#) add programming to a phantom button 1
a) Integration ID – The Integration ID of the device
b) Component Number – Always ‘0’ for Shade
c) Level – The level to which the shade being
programmed will go on activation of this button
d) Fade – The time the zone takes to reach the
level specified (maximum 4 hours)
1
e) Delay – The time until the Shade/Zone begins
to change (maximum 4 hours)
Set (#) add scene programming to a phantom
button
2 a) Integration ID
b) Component Number (GRAFIK Eye QS Scene
controller, Energi Savr Node area
2
)
c) Scene Number
Set (#) clear programming from a phantom
button
3
3 None
Set (#) configure Stop-If-Moving functionality
4
4 0 = Stop-If-Moving Off
1 = Stop-If-Moving On
Set (#) add programming to a phantom button
(Venetian blind, lift and tilt levels)
5 a) Venetian Integration ID
b) Component Number (always 0)
c) Lift level
d) Tilt level
Set (#) add programming to a phantom button
(Venetian blind, tilt only)
6 a) Venetian Integration ID
b) Component Number (always 0)
c) Tilt level
Set (#) add programming to a phantom button
(Venetian blind, lift only)
7 a) Venetian Integration ID
b) Component Number (always 0)
c) Lift level
NOTES
A maximum of 500 programming assignments can be made in the QSE-CI-NWK-E.
1. Not available for Shades.
2. If a device’s Zone is already assigned to the button, you cannot program a Scene for that button. If a Scene is already
programmed for this button for a device, you cannot program another Zone for this button.
3. Use button number 0 to clear programming from all buttons.
4. Use button number 0 to configure Stop-If-Moving functionality on all buttons.
PROGRAMMING Command Formats
Integration ID or Serial # of
the QSE-CI-NWK being used
Use “PROGRAMMING Command-specific fields” tables
to complete these command fields.
Operation
Phantom Button Number
(can be 1
100)
Command
#PROGRAMMING, 1, Button Number, Action Number, Parameters
Continued on next page…